Carrier 58PHA/PHX instruction manual Chimney Inspection Chart

Page 29

CHIMNEY INSPECTION CHART

For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211

Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian

installation Code CSA-B149.1 in Canada.

Crown

 

Rebuild

condition:

Yes

Missing mortar

 

crown.

 

or brick?

 

 

No

 

 

 

 

 

 

 

 

Is chimney

 

No

 

 

 

 

 

 

property lined with

 

 

 

 

 

 

 

 

 

 

 

 

 

clay tile liner?

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Is

 

No

 

Repair

Reline

 

 

 

liner and top

 

 

liner or top seal

 

 

 

seal in good

 

 

or reline chimney as

 

 

 

 

condition?

 

 

 

necessary.

 

 

 

 

Yes

 

 

 

Repair

 

 

 

 

Debris

 

 

 

Mortar

 

 

 

 

in cleanout?

 

Yes

 

Yes

Remove mortar

 

Mortar, tile, metal vent,

 

 

or tile

 

and tile debris

 

fuel oil residue?

 

 

debris?

 

 

 

 

 

 

 

 

No

Remove metal vent

No

 

 

 

 

 

 

or liner.

 

 

 

 

 

 

 

 

 

 

 

 

 

Clay

 

Yes

 

 

 

 

 

 

tile misalignment,

 

 

 

 

 

 

missing sections,

 

 

 

 

 

 

 

gaps?

 

 

 

 

Consult

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part B of

 

Not Suitable

 

No

 

 

 

chimney adapter venting

 

 

 

 

 

 

 

 

 

 

 

No

instructions for

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

application

 

 

 

 

 

 

 

Is chimney

suitability.

 

 

 

Condensate

 

 

 

 

 

 

Line chimney with property

 

 

lined with properly

Suitable

 

 

 

 

 

 

sized, listed flexible metal

drainage at bottom

 

sized, listed liner or

 

 

 

of chimney?

 

 

Yes

 

 

liner or Type-B vent per

 

 

Type-B vent?

 

 

 

Yes

 

 

 

 

NFGC or NSCNGPIC Vent

 

 

 

 

Install chimney

Sizing Tables and liner or

 

 

 

 

 

vent manufacturer’s

No

 

 

 

 

adapter per

 

 

 

 

 

 

Installation instructions.

 

 

 

 

instructions.

Not Suitable

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Chimney

 

 

 

Consult

 

 

Is chimney

No

Part C of

 

exposed to

 

Suitable

 

to be dedicated to

 

chimney adapter venting

outdoors below

 

a single

 

instructions for

 

roof line?

Yes

furnace?

 

application

 

 

 

 

 

suitability

 

No

 

 

 

 

Install chimney

 

 

 

 

 

adapter per

 

 

 

 

 

instructions.

Chimney is

 

 

 

 

 

acceptable for use.

 

 

 

 

 

A03206

Fig. 33 - Chimney Inspection Chart

58PHA

29

Image 29
Contents Ama Furnace Reliability Hazard Safety ConsiderationsCUT Hazard IntroductionClearances to Combustibles Codes and StandardsVenting Electrostatic Discharge ESD Precautions ProcedureCarbon Monoxide Poisoning Hazard LocationGeneral Personal Injury AND/OR Property Damage Hazard Electrical Operation HazardFire Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Location Relative to Cooling EquipmentACH Combination of Indoor and Outdoor Air InstallationBottom Return Air Inlet Side Return Air InletLeveling Legs Downflow InstallationA08556 Suspended Furnace Support Opening Dimensions In. mmPlatform Furnace Support Roll-Out ProtectionAIR Ducts Filter Arrangement Carbon Monoxide and Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsUpflowdownflow Horizontal Horizontal Suspension with Straps Furnace Overheat Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Maximum Capacity of Pipe Air Delivery CFM With FilterUpflow Return Air Configurations and Restrictions Horizontal Return Air Configurations and Restrictions Electrical Shock and Fire Hazard Electrical DataElectrical Connections Electrical Shock Hazard Furnace MAY not Operate WiringBOX Relocation Electrical Connection to J-BOXBX Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXAccessories VentingFurnace Control Masonry Chimney Requirements General Venting RequirementsSingle-Stage Furnace with Single-Speed Air Con Ditioner Humidfier Internal Area of Chimney Appliance Application RequirementsChimney Inspection Chart Sidewall Venting Additional Venting RequirementsBurn Hazard Upflow Application-Vent Elbow Up See Notes 1,2,4,5,7,8,9 on See Notes 1,2,4,5,7,8,9 Venting Notes for Figures Using Tin Snips to Cut Tie PointsRounded End of Knockout Furnace Damage Hazard START-UP, ADJUSTMENT, and Safety CheckFire and Explosion Hazard Altitude Derate Multiplier for U.S.A CanadaFollow exclusively the National Fuel Gas Code Gas Control Valve Furnace Overheating Hazard Check Safety ControlsSpeed Selection Gas Rate Cu Ft./Hr ChecklistA08220 A08220A Electrical Controls and Wiring Electrical Shock Hazard Service and Maintenance ProceduresFIRE, INJURY, or Death Hazard Electrical SHOCK, Fire or Explosion HazardA08221 Service Cleaning AND/OR Replacing AIR Filter Care and Maintenance Fire or Explosion HazardCarbon Monoxide Poisoning Fire Hazard Filter Size Information In. / mmUnit Damage Hazard Cleaning Heat ExchangerIgniter Position-Side View Sequence of Operation Cleaning Heat Exchanger CellThermidistat Mode Cooling ModeContinuous Blower Mode Two-Speed CoolingHeat pump Wiring DiagramsTroubleshooting Wiring Diagram Troubleshooting Guide Catalog No 58PHA---03SI