SMasonry acid washing materials
All
MINIMUM TO BURNERS
A93044
Fig. 5 - Installation in a Garage
!WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
When the furnace is installed in a residential garage, the burners and ignition sources must be located at least 18 inches above the floor. The furnace must be located or protected to avoid damage by vehicles. When the furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, the furnace must be installed in accordance with the NFGC or
!CAUTION
PERSONAL INJURY AND/OR PROPERTY DAMAGE HAZARD
Improper use or installation of this furnace may cause premature furnace component failure.
This gas furnace may be used for heating buildings under construction provided that:
58PHA
Table 2 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
|
|
|
|
|
|
|
| |
| TWO HORIZONTAL DUCTS | SINGLE DUCT OR OPENING | TWO OPENINGS OR VERTICAL | |||||
| DUCTS |
| ||||||
FUR- |
| (1 SQ. IN./2,000 BTUH) | (1 SQ. IN./3,000 BTUH) |
| ||||
| (1 SQ. IN./4,000 BTUH) | |||||||
NACE |
| (1,100 SQ. MM/KW) | (734 SQ. MM/KW) | (550 SQ. MM/KW) | ||||
INPUT |
|
|
|
|
|
|
|
|
Free Area of Opening | Round Duct | Free Area of Open- | Round Duct | Free Area of |
| Round Duct | ||
(BTUH) |
| |||||||
and Duct | Diameter | ing and Duct | Diameter | Opening and Duct |
| Diameter | ||
|
| |||||||
| (sq. in. / sq. mm) | (in./mm) | (sq. In. / sq. mm) | (in. / mm) | (sq. In. / sq. mm) |
| (In./mm) | |
|
|
|
|
|
|
|
|
|
44,000 | 22 | (14193) | 6 (152) | 14.7 (9484) | 5 (127) | 11 (7097) |
| 4 (102) |
66,000 | 33 | (21290) | 7 (178) | 22 (14193) | 6 (152) | 16.5 (10645) |
| 5 (127) |
88,000 | 44 | (28387) | 8 (203) | 29.3 (18903) | 7 (178) | 22 (14193) |
| 6 (152) |
110,000 | 55 | (35484) | 9 (229) | 36.7 (23677) | 7 (178) | 27.5 (17742) |
| 6 (152) |
132,000 | 66 | (42581) | 10 (254) | 44 (28387) | 8 (203) | 33 (21290) |
| 7 (178) |
EXAMPLES: Determining Free Area
FURNACE |
| WATER HEATER |
| TOTAL INPUT |
|
|
|
110,000 | + | 30,000 | = (140,000 divided by 4,000) | = | 35.0 | Sq. In. for each two Vertical Ducts or Openings | |
66,000 | + | 40,000 | = | (106,000 divided by 3,000) | = | 35.3 | Sq. In. for a Single Duct or Opening |
88,000 | + | 30,000 | = | (118,000 divided by 2,000) | = | 59.0 | Sq. In. for each of two Horizontal Ducts |
7