Carrier 58PHA/PHX instruction manual Electrostatic Discharge ESD Precautions Procedure, Venting

Page 5

Max 85ºF/ 29ºC

Min 60ºF / 16ºC

A02055

Fig. 3 - Return Air Temperature

General Installation

SUS: Current edition of the NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; (www.NFPA.org) or for only the NFGC, contact the American Gas Association, 400 N. Capitol Street, N.W., Washington, DC 20001 (www.AGA.org).

SCANADA: CAN/CSA-B149.1-05. For a copy, contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3 Canada.

Combustion and Ventilation Air

SUS: NGFC NFPA54/ANSI Z223.1-2006 Section 9.3, Air for Combustion and Ventilation.

SCANADA: Part 8 of CAN/CSA-B149.1-05, Venting Systems and Air Supply for Appliances.

Duct Systems

SUS and CANADA: Air Conditioning Contractors Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter 35 or 2004 HVAC Systems and Equipment Handbook Chapters 9 and 16.

Acoustical Lining and Fibrous Glass Duct

SUS and CANADA: current edition of SMACNA and NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts

Gas Piping and Gas Pipe Pressure Testing

SUS: NFGC NFPA54/ANSI Z223.1-2006; chapters 5, 6, 7, and 8 and National Plumbing Codes.

SCANADA: CAN/CSA-B149.1-05 Parts 4, 5, and 6 Appendices A, B, E, and H.

Electrical Connections

SUS: National Electrical Code (NEC) ANSI/NFPA 70-2008.

SCANADA: Canadian Electrical Code CSA C22.1.

Venting

SUS: NFGC NFPA 54 / ANSI Z223.1-2006; Chapters 12 and 13.

SCANADA: CAN/CSA-B149.1-05 Part 8 and Appendix C.

ELECTROSTATIC DISCHARGE (ESD)

PRECAUTIONS PROCEDURE

!CAUTION

FURNACE RELIABILITY HAZARD

Improper installation or service of furnace may cause premature furnace component failure.

Electrostatic discharge can affect electronic components. Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.

1.Disconnect all power to the furnace. Multiple disconnects maybe required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR

TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.

2.Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Firmly touch the clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.

3.After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing to recharge your body with static electricity (for example; DO NOT move or shuffle your feet, do not touch ungrounded objects, etc.).

4.If you touch ungrounded objects (and recharge your body with static electricity), firmly touch a clean, unpainted metal surface of the furnace again before touching control or wires.

5.Use this procedure for installed and uninstalled (ungrounded) furnaces.

58PHA

5

Image 5
Contents Ama Furnace Reliability Hazard Safety ConsiderationsCUT Hazard IntroductionClearances to Combustibles Codes and StandardsVenting Electrostatic Discharge ESD Precautions ProcedureCarbon Monoxide Poisoning Hazard LocationGeneral Personal Injury AND/OR Property Damage Hazard Electrical Operation HazardFire Hazard AIR for Combustion VentilationFurnace Corrosion Hazard Location Relative to Cooling EquipmentACH Combination of Indoor and Outdoor Air InstallationBottom Return Air Inlet Side Return Air InletLeveling Legs Downflow InstallationA08556 Suspended Furnace Support Opening Dimensions In. mmPlatform Furnace Support Roll-Out ProtectionAIR Ducts Filter Arrangement Carbon Monoxide and Poisoning HazardGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsUpflowdownflow Horizontal Horizontal Suspension with Straps Furnace Overheat Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Maximum Capacity of Pipe Air Delivery CFM With FilterUpflow Return Air Configurations and Restrictions Horizontal Return Air Configurations and Restrictions Electrical Shock and Fire Hazard Electrical DataElectrical Connections Electrical Shock Hazard Furnace MAY not Operate WiringBOX Relocation Electrical Connection to J-BOXBX Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXAccessories VentingFurnace Control Masonry Chimney Requirements General Venting RequirementsSingle-Stage Furnace with Single-Speed Air Con Ditioner Humidfier Internal Area of Chimney Appliance Application RequirementsChimney Inspection Chart Sidewall Venting Additional Venting RequirementsBurn Hazard Upflow Application-Vent Elbow Up See Notes 1,2,4,5,7,8,9 on See Notes 1,2,4,5,7,8,9 Venting Notes for Figures Using Tin Snips to Cut Tie PointsRounded End of Knockout Furnace Damage Hazard START-UP, ADJUSTMENT, and Safety CheckFire and Explosion Hazard Altitude Derate Multiplier for U.S.A CanadaFollow exclusively the National Fuel Gas Code Gas Control Valve Furnace Overheating Hazard Check Safety ControlsSpeed Selection Gas Rate Cu Ft./Hr ChecklistA08220 A08220A Electrical Controls and Wiring Electrical Shock Hazard Service and Maintenance ProceduresFIRE, INJURY, or Death Hazard Electrical SHOCK, Fire or Explosion HazardA08221 Service Cleaning AND/OR Replacing AIR Filter Care and Maintenance Fire or Explosion HazardCarbon Monoxide Poisoning Fire Hazard Filter Size Information In. / mmUnit Damage Hazard Cleaning Heat ExchangerIgniter Position-Side View Sequence of Operation Cleaning Heat Exchanger CellThermidistat Mode Cooling ModeContinuous Blower Mode Two-Speed CoolingHeat pump Wiring DiagramsTroubleshooting Wiring Diagram Troubleshooting Guide Catalog No 58PHA---03SI