Carrier 58PHA/PHX Service and Maintenance Procedures, FIRE, INJURY, or Death Hazard

Page 43

SERVICE AND MAINTENANCE

PROCEDURES

!WARNING

FIRE, INJURY, OR DEATH HAZARD

Failure to follow this warning could result in personal injury, death and/or property damage.

The ability to properly perform maintenance on this equipment requires certain knowledge, mechanical skills, tools, and equipment. If you do not possess these, do not attempt to perform any maintenance on this equipment other than those procedures recommended in the User’s Manual.

!WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury or death, or property damage.

Before servicing, disconnect all electrical power to furnace. Verify proper operation after servicing.

!CAUTION

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in improper furnace operation or failure of furnace.

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

INTRODUCTION

GENERAL

These instructions are written as if the furnace is installed in an upflow application. An upflow furnace application is where the blower is located below the combustion and controls section of the furnace, and conditioned air is discharged upward. Since this furnace can be installed in any of the 4 positions shown in Fig. 4, you must revise your orientation to component location accordingly.

ELECTRICAL CONTROLS AND WIRING

!CAUTION

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

There may be more than one electrical supply to the furnace. Check accessories and cooling unit for additional electrical supplies that must be shut off during furnace servicing.

The electrical ground and polarity for 115-v wiring must be properly maintained. Refer to Fig. 25 for field wiring information and to Fig. 59 for furnace wiring information.

NOTE: If the polarity is not correct, the STATUS LED on the control will flash rapidly and prevent the furnace from heating. The control system also requires an earth ground for proper operation of the control and flame-sensing electrode.

The 24-v circuit contains an automotive-type, 3-amp.. fuse located on the control. (See Fig. 24.) Any shorts of the 24-v wiring during installation, service, or maintenance will cause this fuse to blow. If fuse replacement is required, use ONLY a 3-amp. fuse. The control LED will display status code 24 when fuse needs to be replaced.

Proper instrumentation is required to service electrical controls. The control in this furnace is equipped with a Status Code LED (Light-Emitting Diode) to aid in installation, servicing, and troubleshooting. It can be viewed through the sight glass in blower access door. The furnace control LED is either ON continuously, rapid flashing, or a code composed of 2 digits. The first digit is the number of short flashes, the second digit is the number of long flashes.

For an explanation of status codes, refer to service label located on blower access door or Fig. 55 and the troubleshooting guide which can be obtained from your distributor.

See Fig. 60, a brief Troubleshooting Guide.

For Controls With an Amber LED

The stored status code will not be erased from the control memory, if 115- or 24-v power is interrupted.

1.To retrieve status code, proceed with the following:

NOTE: NO thermostat signal may be present at control, and all blower-OFF delays must be completed.

a.Leave 115-v power to furnace turned on.

b.Remove outer access door.

c.Look into blower access door sight glass for current LED status. Removing blower access door will open blower access door switch and terminate 115-v power to control so that status code is not displayed.

d.BRIEFLY remove insulated terminal wire from the draft safeguard (DSS) switch until LED goes out, then reconnect it.

NOTE: If wire to LS or DSS is disconnected longer than 4 sec, main blower starts, and retrieval request is ignored.

2.When above items have been completed, the LED flashes status code 4 times. Record this status code for further troubleshooting.

3.Check LED status. If no previous faults in history, control will flash status code 11.

58PHA

43

Image 43
Contents Ama Furnace Reliability Hazard Safety ConsiderationsCUT Hazard IntroductionClearances to Combustibles Codes and StandardsVenting Electrostatic Discharge ESD Precautions ProcedureGeneral LocationCarbon Monoxide Poisoning Hazard Personal Injury AND/OR Property Damage Hazard Electrical Operation HazardLocation Relative to Cooling Equipment AIR for Combustion VentilationFire Hazard Furnace Corrosion HazardACH Side Return Air Inlet InstallationCombination of Indoor and Outdoor Air Bottom Return Air InletLeveling Legs Downflow InstallationA08556 Roll-Out Protection Opening Dimensions In. mmSuspended Furnace Support Platform Furnace SupportDuctwork Acoustical Treatment Supply Air Connections Filter Arrangement Carbon Monoxide and Poisoning HazardAIR Ducts General RequirementsUpflowdownflow Horizontal Horizontal Suspension with Straps GAS Piping Fire or Explosion Hazard Return Air ConnectionsFurnace Overheat Hazard Maximum Capacity of Pipe Air Delivery CFM With FilterUpflow Return Air Configurations and Restrictions Horizontal Return Air Configurations and Restrictions Electrical Connections Electrical Shock Hazard Electrical DataElectrical Shock and Fire Hazard Electrical Connection to J-BOX WiringFurnace MAY not Operate BOX RelocationVenting Power Cord Installation in Furnace J-BOXBX Cable Installation in Furnace J-BOX AccessoriesFurnace Control Masonry Chimney Requirements General Venting RequirementsSingle-Stage Furnace with Single-Speed Air Con Ditioner Humidfier Internal Area of Chimney Appliance Application RequirementsChimney Inspection Chart Burn Hazard Additional Venting RequirementsSidewall Venting Upflow Application-Vent Elbow Up See Notes 1,2,4,5,7,8,9 on See Notes 1,2,4,5,7,8,9 Venting Notes for Figures Using Tin Snips to Cut Tie PointsRounded End of Knockout Fire and Explosion Hazard START-UP, ADJUSTMENT, and Safety CheckFurnace Damage Hazard Follow exclusively the National Fuel Gas Code CanadaAltitude Derate Multiplier for U.S.A Gas Control Valve Speed Selection Check Safety ControlsFurnace Overheating Hazard Gas Rate Cu Ft./Hr ChecklistA08220 A08220A Electrical SHOCK, Fire or Explosion Hazard Service and Maintenance ProceduresElectrical Controls and Wiring Electrical Shock Hazard FIRE, INJURY, or Death HazardA08221 Service Filter Size Information In. / mm Care and Maintenance Fire or Explosion HazardCleaning AND/OR Replacing AIR Filter Carbon Monoxide Poisoning Fire HazardUnit Damage Hazard Cleaning Heat ExchangerIgniter Position-Side View Sequence of Operation Cleaning Heat Exchanger CellTwo-Speed Cooling Cooling ModeThermidistat Mode Continuous Blower ModeTroubleshooting Wiring DiagramsHeat pump Wiring Diagram Troubleshooting Guide Catalog No 58PHA---03SI