Carrier 58PHA/PHX instruction manual Gas Control Valve

Page 38

58PHA

c.Measure time (in sec) for gas meter to complete 1 revolution and note reading. The 2 or 5 cubic feet dial provides a more accurate measurement of gas flow.

d.Refer to Table 12 for cubic ft. of gas per hr.

e.Multiply gas rate (cu ft./hr) by heating value (Btuh/cu ft.) to obtain input.

If clocked rate does not match required input from Step 1, increase manifold pressure to increase input or decrease manifold pressure to decrease input. Repeat steps b through e until correct input is achieved. Reinstall regulator seal cap on gas valve.

5.Set temperature rise. The furnace must operate within the temperature rise ranges specified on the furnace rating plate. Do not exceed temperature rise range specified on unit rating plate. Determine the temperature rise as follows:

NOTE: Blower access door must be installed when taking temperature rise reading. Leaving blower access door off will result in incorrect temperature measurements.

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Disconnect 115-v electrical power before changing speed tap.

a.Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see radiant heat from heat exchangers. Radiant heat affects temperature rise readings. This practice is particularly important with straight-run ducts.

b.When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.

NOTE: Blower access door must be installed for proper temperature rise measurement.

NOTE: If the temperature rise is outside this range, first check: (1.) Gas input for heating operation.

(2.) Derate for altitude if applicable.

(3.) Return and supply ducts for excessive restrictions causing static pressures greater than 0.50-in. wc.

(4.) Dirty filter.

c.Reinstall blower access door if removed.

d.Turn gas valve ON/OFF switch to ON.

e.Adjust air temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise

f.Turn thermostat down below room temperature and remove blower access door.

g.To change motor speed selection for heating, remove blower motor lead from control HEAT terminal (See Fig. 24.) Select desired blower motor speed lead from one of the other terminals and relocate it to the HEAT terminal (See Table 11 for lead color identification). Reconnect original lead to SPARE terminal.

h.Repeat steps a through e.

i.When correct input rate and temperature rise is achieved, turn gas valve ON/OFF switch to OFF.

j.Remove manometer or similar device from gas valve.

k.Reinstall manifold pressure tap plug in gas valve.

A06666

Fig. 52 - Gas Control Valve

BURNER

ORIFICE

A93059

Fig. 53 - Orifice Hole

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury, death, and/or property damage.

Reinstall manifold pressure tap plug in gas valve to prevent gas leak.

38

Image 38
Contents Ama Safety Considerations Furnace Reliability HazardIntroduction CUT HazardCodes and Standards Clearances to CombustiblesElectrostatic Discharge ESD Precautions Procedure VentingCarbon Monoxide Poisoning Hazard LocationGeneral Electrical Operation Hazard Personal Injury AND/OR Property Damage HazardFurnace Corrosion Hazard AIR for Combustion VentilationFire Hazard Location Relative to Cooling EquipmentACH Bottom Return Air Inlet InstallationCombination of Indoor and Outdoor Air Side Return Air InletDownflow Installation Leveling LegsA08556 Platform Furnace Support Opening Dimensions In. mmSuspended Furnace Support Roll-Out ProtectionGeneral Requirements Filter Arrangement Carbon Monoxide and Poisoning HazardAIR Ducts Ductwork Acoustical Treatment Supply Air ConnectionsUpflowdownflow Horizontal Horizontal Suspension with Straps Furnace Overheat Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Air Delivery CFM With Filter Maximum Capacity of PipeUpflow Return Air Configurations and Restrictions Horizontal Return Air Configurations and Restrictions Electrical Shock and Fire Hazard Electrical DataElectrical Connections Electrical Shock Hazard BOX Relocation WiringFurnace MAY not Operate Electrical Connection to J-BOXAccessories Power Cord Installation in Furnace J-BOXBX Cable Installation in Furnace J-BOX VentingFurnace Control General Venting Requirements Masonry Chimney RequirementsSingle-Stage Furnace with Single-Speed Air Con Ditioner Humidfier Appliance Application Requirements Internal Area of ChimneyChimney Inspection Chart Sidewall Venting Additional Venting RequirementsBurn Hazard Upflow Application-Vent Elbow Up See Notes 1,2,4,5,7,8,9 on See Notes 1,2,4,5,7,8,9 Using Tin Snips to Cut Tie Points Venting Notes for FiguresRounded End of Knockout Furnace Damage Hazard START-UP, ADJUSTMENT, and Safety CheckFire and Explosion Hazard Altitude Derate Multiplier for U.S.A CanadaFollow exclusively the National Fuel Gas Code Gas Control Valve Furnace Overheating Hazard Check Safety ControlsSpeed Selection Checklist Gas Rate Cu Ft./HrA08220 A08220A FIRE, INJURY, or Death Hazard Service and Maintenance ProceduresElectrical Controls and Wiring Electrical Shock Hazard Electrical SHOCK, Fire or Explosion HazardA08221 Service Carbon Monoxide Poisoning Fire Hazard Care and Maintenance Fire or Explosion HazardCleaning AND/OR Replacing AIR Filter Filter Size Information In. / mmCleaning Heat Exchanger Unit Damage HazardIgniter Position-Side View Cleaning Heat Exchanger Cell Sequence of OperationContinuous Blower Mode Cooling ModeThermidistat Mode Two-Speed CoolingHeat pump Wiring DiagramsTroubleshooting Wiring Diagram Troubleshooting Guide Catalog No 58PHA---03SI