Absorption Chiller Types

notes

separate from the absorbent solution. As the refrigerant boils away, the solution becomes concentrated and returns to the absorber.

The hot refrigerant vapor produced in the high-temperature generator migrates to the low-temperature generator where it flows through the tubes that are immersed in a dilute solution. The solution absorbs heat from the high- temperature refrigerant vapor, causing the refrigerant in the low-temperature generator to boil and separate from the absorbent solution. As that refrigerant boils away, the concentration of the solution increases and it returns to the absorber.

The low-temperature refrigerant vapor produced in the low-temperature generator migrates to the cooler condenser. Additionally, the liquid refrigerant that condensed inside the tubes of the low-temperature generator flows into the condenser.

condenser

low-temperature

 

cooling

 

 

 

generator

 

 

 

water

 

 

 

 

evaporator

 

chilled

 

 

 

 

 

 

water

 

low-temperature

 

expansion

 

heat exchanger

 

 

 

device

 

 

 

 

absorber

 

 

 

absorber

 

evaporator spray pump

 

spray pump

 

low-temperature

Figure 33

 

 

generator pump

 

 

 

Next, the refrigerant travels through the condenser, expansion device, evaporator, and absorber in a manner similar to refrigerant travel in the indirect-fired double-effect absorption chiller.

The low-temperature generator pump returns the dilute absorbent solution to the low-temperature generator to be reconcentrated. This cool dilute solution passes through the low-temperature heat exchanger to be preheated by the hot concentrated solution returning from the two generators.

28

TRG-TRC011-EN

Image 33
Contents Air Conditioning Clinic Absorption Water Chillers Absorption Water Chillers Preface Contents TRG-TRC004-EN Introduction TRG-TRC011-EN Period one Absorption Refrigeration CyclePeriod one Reject heat Heat energy Absorption System Fluids High affinity for water refrigerant Components of the Absorption Cycle Conditions Steam or Hot waterrefrigerant vapor Generator Condenser Refrigerant then flows into the evaporator pan Absorber spray pump Solution Heat Exchanger Dilute Generator pump Equilibrium Chart Heat Solution temperature Period two Absorption Chiller TypesSingle-Effect Chiller Absorber Evaporator spray pump Spray pump Generator pump Double-Effect Chiller Vapor Low Temperature condenser Cooling Generator Water Evaporator Absorber Low-temperature generator pump Generator pump Absorption Chiller Types Direct-Fired Chiller Evaporator High-temperature high-temperature Generatorgenerator pump Chiller/Heater Absorption Chiller Types Changeover Absorption Chiller Types Period three Capacity ControlPeriod three Energy valve Generator Crystallization 10C 37.8C Capacity Control Capacity Control Capacity Control Heat exchanger bypass Evaporator pan Purge System Isolation valve Period four Maintenance ConsiderationsPeriod four Maintenance Considerations Test run with alternate fuel, if dual-fuel burner Maintenance Considerations Maintenance Considerations Corrosion inhibitor and performance additive recommendations Period five Application ConsiderationsCooling-Water Temperature Limitations Combination Chiller Plants 58F Special Considerations for Direct-Fired Chillers Application Considerations Equipment Rating Standards Period six ReviewPeriod six Review Review Review Questions for Period QuizQuiz TRG-TRC011-EN Answers Glossary Glossary Glossary Trane Company