period five
Application Considerations
notes
▲
◆Combustion air ducted from outside the machinery room
◆Refrigerant vapor detector to shut down combustion process in the event of a refrigerant leak
Figure 66
In general, ASHRAE Standard
This code does not apply where water is the primary refrigerant.
Section 8.13.6 of the Standard, however, does affect
No open flames that use combustion air from the machinery room shall be installed where any refrigerant is used … Combustion equipment shall not be installed in the same machinery room with
(a)Combustion air is ducted from outside the machinery room and sealed in such a manner as to prevent any refrigerant leakage from entering the combustion chamber, or
(b)A refrigerant vapor detector is employed to automatically shut down the combustion process in the event of refrigerant leakage.
When halocarbon refrigerants (such as
Exception (a) allows combustion air to be ducted to the
58 |
|