A.6 Operation Notes, Continued

Database Mismatch Parameters, continued

If a mismatch is detected, only the slots (PVs) that have the mismatch will have their PV value set to not a number (NAN) and their STATE parameter on the Detail display will show DBCHANGE. Note that an asterisk “*” will appear next to the PV number or Number of PVs on the other slots to indicate that there is a problem.

DECONF Changes

A change in the DECONF parameter such as turning PV2, 3, or 4 ON, which is equivalent to building a point for the given transmitter PV, can only be downloaded from the Detail display for PV number 1. Enter identical tag names for as many PVs as desired (sequentially, up to 4) and then download from the master slot. If you try to download a DECONF change from the Detail display for PV number 2, 3 or 4, you will get an error message as shown in Figure A-7.

Figure A-7 Example of DECONF Download Error Message.

 

 

 

 

23 Jun 98 11:15:23 6

F101 SMV SLOT 2 - STATIC PRESS

 

03 UNIT 01

CONFIG PAGE

_________________ CONFIGURATION DATA ________________

PVFORMAT

01

PVCHAR

 

LINEAR

PVLOPR

NOACTION

PVSRCOPT

ALL

SENSRTYP SPT_AP PVROCPPR NOACTION

PVCLAMP

CLAMP

PIUOTDCF

OFF

PVROCNPR NOACTION

PVALDR

ONE

BADPVPR

 

LOW

 

 

 

PVALDEBEU

2.0000

PVHHPR NOACTION

 

 

 

INPTDIR

REVERSE

PVHIPR NOACTION

 

 

 

LOCUTOFF

-------

PVLLPR NOACTION

 

 

 

______________ SMART TRANSMITTER DATA ______________

STITAG

FT3011

PVRAW

------

SECVAR

------

SENSRTYP

SPT_AP

URL

------

DAMPING

0.00000

PVCHAR

LINEAR

URV

------

SERIALNO

 

CJTACT

OFF

LRV

------

STISWVER

 

PIUOTDCF

OFF

LUL

------

STATE

 

LOADFAIL

DECONF

Pv_Db

STI_EU

 

PSI

COMMAND

NONE

TRANSMITTER SCRATCH PAD:

 

 

 

 

 

TRANSMITTER STATUS

: COMMAND ALLOWED ONLY ON FIRST

 

 

SLOT OF MULTIPLE PV XMTRS

 

 

 

 

 

 

 

2 OF 2

Message means you can only initiate DECONF download from Detail display for slot 1 or PV number 1.