11.4Diagnostic Messages, Continued

Diagnostic Messages,

Table 34

Informational Status Message Table

continued

 

 

SMV Status

6-3

SCT Status Message

SFC Display Message

TDC Status Message

 

 

 

 

2 Wire TC PV3

STATUS

TAG ID.

2 WIRE TC PV3

 

2 WIRE

TC PV3

 

 

 

 

 

Possible Cause

PV3 input is being provided by

2-wire Thermocouple (T/C) type.

What to Do

Nothing – Information only. However, this may indicate a problem if sensor type does not match the sensor physically connected to transmitter.

6-0

6-1

2 Wire RTD PV3

3 Wire RTD PV3

STATUS TAG ID. 2 WIRE RTD PV3

STATUS TAG ID. 3 WIRE RTD PV3

2 WIRE RTD PV3

3 WIRE RTD PV3

PV3 input is being provided by 2-wire RTD type.

PV3 input is being provided by 3-wire RTD type.

Nothing – Information only. However, this may indicate a problem if number of wires displayed does not match number of RTD leads physically connected to transmitter; or if sensor type should be thermocouple.

Nothing – Information only. However, this may indicate a problem if number of wires displayed does not match number of RTD leads physically connected to transmitter; or if sensor type should be thermocouple.

6-2

4 Wire RTD PV3

STATUS TAG ID. 4 WIRE RTD PV3

4 WIRE RTD PV3

PV3 input is being provided by 4-wire RTD type.

Nothing – Information only. However, this may indicate a problem if number of wires displayed does not match number of RTD leads physically connected to transmitter; or if sensor type should be thermocouple.

4-3

PV2 Sensor = AP

-

STATUS 4-3

Sensor type for the current SMV Nothing – Information only. is absolute pressure.

4-4

-

PV2 Sensor = GP

Write Protected

-

URV 1 . TAG ID.

WRITE PROTECTED

STATUS 4-4

-

Sensor type for the current SMV is gauge pressure.

The value could not be written because the transmitter is write protected.

Nothing – Information only.

The hardware jumper within the device must be repositioned in order to permit write operations.