4.5 Wiring SMV 3000 Transmitter, Continued

Wiring connections,

Table 7

continued

Step

3

Wiring the Transmitter, Continued

Action

Feed temperature sensor input leads through conduit entrance in housing. Strip 1/4 inch (6.35 mm) of insulation from input leads.

If input is from …

Then…

2-wire RTD

connect RTD leads to

 

terminals 1 and 3.

 

See Figure 15.

3-wire RTD

connect RTD leads to

 

terminals 1, 2, and 3.

 

See Figure 15.

4-wire RTD

connect RTD leads to

 

terminals 1, 2, 3, and 4. See

 

Figure 16.

2-wire Thermocouple

connect minus (–) lead to

 

terminal 1 and plus (+) lead to

 

terminal 3. See Figure 16.

4

5

Feed loop power leads through conduit entrance on other side of electronics housing opposite RTD wiring entrance.

 

ATTENTION

The transmitter accepts up to 16 AWG (1.5 mm

diameter) wire.

 

 

 

 

Strip 1/4 inch (6.35 mm) of insulation from leads. Observing polarity, connect positive loop power lead to SIGNAL + terminal and negative loop power lead to SIGNAL – terminal.

Example - Connecting loop power to transmitter.

_ Loop

+ Power

 

 

 

 

1

 

 

2 TC 3

4

 

 

 

METER

L

SIGNAL

 

+

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– + – +

TEST SIG

6

If you have an optional analog meter, be sure jumper strap is removed from across METER terminals, yellow lead from meter is connected to METER – terminal and red lead is connected to METER + terminal.

See control drawing 51404251 (for intrinsically safe installations) or wiring diagram 51404250 (non-intrinsically safe) included in Section 13.

Continued on next page

1/99

SMV 3000 Transmitter User’s Manual

33

Page 45
Image 45