11.4Diagnostic Messages, Continued

Diagnostic Messages,

Table 32

Non-Critical Status Diagnostic Message Table, continued

continued

 

 

SMV Status

SCT Status Message SFC Display Message TDC Status Message

Possible Cause

What to Do

 

 

5-5

Input Mode PV2 (AP)

STATUS TAG ID.#

INPUT MODE PV2

 

INPUT MODE PV2

 

 

 

 

Transmitter is simulating input for PV2.

Exit Input mode:

SCT – Press “Clear Input Mode” button on the AP InCal tab.

SFC – Press [SHIFT], [INPUT], and [CLR] keys.

5-6

5-7

2-0

2-7

Input Mode PV3 (Temp)

Input Mode PV4 (Flow)

Meter Body Sensor Over

Temperature

No DAC Temp Comp

Or

DAC Temperature

Compensation data is

corrupt

STATUS TAG ID.# INPUT MODE PV3

STATUS TAG ID.# INPUT MODE PV4

STATUS TAG ID.# M.B. OVERTEMP

STATUS TAG ID.# NO DAC TEMPCOMP

INPUT MODE PV3

INPUT MODE PV4

M.B. OVERTEMP

NO DAC TEMP COMP

Transmitter is simulating input for PV3.

Transmitter is simulating input for PV4.

Sensor temperature is too high (>125 ° C). Accuracy and life span may decrease if it remains high.

Failed DAC.

Exit Input mode:

SCT – Press “Clear Input Mode” button on the TEMP InCal tab.

SFC – Press [SHIFT], [INPUT], and [CLR] keys.

Exit Input mode:

SCT – Press “Clear Input Mode” button on the FLOW InCal tab.

SFC – Press [SHIFT], [INPUT], and [CLR] keys.

Take steps to insulate meter body from temperature source.

Replace electronics module.