11.4Diagnostic Messages, Continued

Diagnostic Messages,

Table 32

Non-Critical Status Diagnostic Message Table, Continued

continued

 

 

SMV Status

6-4

SCT Status Message

SFC Display Message

TDC Status Message

Possible Cause

 

 

 

 

 

 

Output Mode PV1 (DP)

STATUS

TAG

ID.#

OUTPUT MODE PV1

Analog transmitter is operating as a

 

OUTPUT

MODE

PV1

 

current source for PV1 output.

 

 

 

 

 

 

 

 

 

What to Do

Exit Output Mode:

SCT – Press “Clear Output Mode” button on the DP OutCal tab.

SFC – Press [OUTPUT] and [CLR] keys.

6-5

6-6

6-7

Output Mode PV2 (SP)

Output Mode PV3

(Temp)

Output Mode PV4 (Flow)

STATUS TAG ID.# OUTPUT MODE PV2

STATUS TAG ID.# OUTPUT MODE PV3

STATUS TAG ID.# OUTPUT MODE PV4

OUTPUT MODE PV2

OUTPUT MODE PV3

OUTPUT MODE PV4

Analog transmitter is operating as a current source for PV2 output.

Analog transmitter is operating as a current source for PV3 output.

Analog transmitter is operating as a current source for PV4 output.

Exit Output Mode:

SCT – Press “Clear Output Mode” button on the AP OutCal tab.

SFC – Press [OUTPUT] and [CLR] keys.

Exit Output Mode:

SCT – Press “Clear Output Mode” button on the TEMP OutCal tab.

SFC – Press [OUTPUT] and [CLR] keys.

Exit Output Mode:

SCT – Press “Clear Output Mode” button on the FLOW OutCal tab.

SFC – Press [OUTPUT] and [CLR] keys.

3-7

PV4 Independent

variable out of range

-

STATUS 3-7

For R250 Laminar Flow transmitters only. Asserted when a PV is not within the range of a term in the laminar Flow equation.

Check the value of every PV against the ranges in the Laminar Flow equation.

Redefine the equation, if necessary.

130

SMV 3000 Transmitter User’s Manual

1/99

Page 142