Sensor Type

Identify and select the type of sensor that is connected to the transmitter as its input for process temperature PV3. This will set the appropriate LRL and URL data in the transmitter automatically.

Table 15 shows the pre-programmed temperature sensor types and the rated measurement range limits for a given sensor selection.

Table 15 Sensor Types for PV3 Process Temperature Input

Sensor Type

Rated Temperature Range Limits

PT100 Dd

Type E

Type J

Type K

Type T

d Factory setting.

°C

-200 to 450

0 to 1000

0 to 1200

-100 to 1250

-100 to 400

°F

-328 to 842

32 to 1832

32 to 2192

-148 to 2282

-148 to 752

ATTENTION

Whenever you connect a different sensor as the transmitter’s input, you must also change the sensor type configuration to agree. Otherwise, range setting errors may result.

1/99

SMV 3000 Transmitter User’s Manual

63