3.2 Considerations for SMV 3000 Transmitter, Continued

RTD requirements

Use a two-, three-, or four-wire platinum 100 ohm (Pt100) Resistance Temperature Detector with rated measurement range limits of –200 to 450 °C (–328 to 842 °F) per DIN 43760 standard (α = 0.00385 //° C) as the input source for the process temperature PV.

Thermocouple requirements

Use one of the thermocouple types listed in Table 4 as the input source for the process temperature.

Table 4

Thermocouple Types for Process Temperature Sensor

 

 

 

 

 

 

 

 

Type

Rated Range Limits

Standard

 

 

 

 

 

 

 

 

 

° C

° F

 

 

 

 

 

 

 

 

 

E

0 to 1000

32 to 1832

IEC584.1

 

 

 

 

 

 

 

 

J

0 to 1200

32 to 2192

IEC584.1

 

 

 

 

 

 

 

 

K

–100 to 1250

–148 to 2282

IEC584.1

 

 

 

 

 

 

 

 

T

–100 to 400

–148 to 752

IEC584.1

 

 

 

 

 

 

 

 

 

 

 

 

16

SMV 3000 Transmitter User’s Manual

1/99

Page 28
Image 28
Honeywell SMV 3000 user manual RTD requirements, Thermocouple requirements, Type Rated Range Limits Standard