11.4Diagnostic Messages, Continued

Diagnostic Messages,

Table 32

Non-Critical Status Diagnostic Message Table, continued

continued

 

 

SMV Status

SCT Status Message

SFC Display Message TDC Status Message

Possible Cause

What to Do

 

 

9-6

3-6

Corrects Active on PV4

Density temperature or pressure out of range

STATUS TAG ID.#

CORR. ACTIVE PV4

CORR. ACTIVE PV4

 

-

STATUS 3-6

 

 

Calculated flow rate PV4 has been calibrated.

Either the temperature (PV3) or the pressure (PV2) is not within the boundaries of SMV steam equation.

The SMV steam equation is defined for pressures between 8 and 3000 psia, and temperature between saturation and 1500 ° F, except above 2000 psia.

Nothing – or do a reset corrects.

Check to see if the PV measurement is correct.

2-2

4-2

Excess Span Correct

PV1

Or

Span Correction is Out

of Limits

Excess Span Correct

PV2

STATUS TAG ID.# EX. SPAN COR PV1

STATUS TAG ID.# EX. SPAN COR PV2

EX. SPAN COR PV1

EX. SPAN COR PV2

SPAN correction factor is outside acceptable limits for PV1 range. Could be that transmitter was in input or output mode during a CORRECT procedure.

SPAN correction factor is outside acceptable limits for PV2 range. Could be that transmitter was in input or output mode during a CORRECT procedure.

Verify calibration.

If error persists, call the Solutions Support Center

Verify calibration.

If error persists, call the Solutions Support Center

8-2

9-2

Excess Span Correct

PV3

Excess Span Correct

PV4

STATUS TAG ID.# EX. SPAN COR PV3

STATUS TAG ID.# EX. SPAN COR PV4

EX. SPAN COR PV3

EX. SPAN COR PV4

SPAN correction factor is outside acceptable limits for PV3 range.

SPAN correction factor is outside acceptable limits for PV4 range.

Verify calibration.

If error persists, call the Solutions Support Center

Verify calibration.

If error persists, call the Solutions Support Center

1/99

SMV 3000 Transmitter User’s Manual

127

Page 139
Image 139
Honeywell user manual SMV 3000 Transmitter User’s Manual 127