Honeywell SMV 3000 AP/GPConf Configuration PV2, Absolute Pressure, STG170, Gauge Pressure

Models: SMV 3000

1 217
Download 217 pages 57.98 Kb
Page 71
Image 71

6.7 AP/GPConf Configuration - PV2

Engineering Units

The AP/GPConf tab card displays the Low Range Value (LRV), Low Range Limit (LRL), Upper Range Value (URV) and Upper Range Limit (URL) for PV2 in the unit of measure selected in the Engineering Units field.

NOTE: Depending on the SMV transmitter model type, PV2 will measure static pressure in either absolute or gauge values.

SMV Models —SMA110 and SMA125

PV2

—Absolute Pressure

—STG170

PV2

—Gauge Pressure

 

 

 

PV2 Engineering Units Select one of the preprogrammed engineering units in Table 13 for display of the PV2 measurements.

Table 13 Pre-programmed Engineering Units for PV2*

Engineering Unit

inH2O @ 39F inH2O @ 68F mmHg @ 0C psi d

kPa

MPa mbar bar g/cm2

Kg/cm2

inHg @ 32F

mmH2O @ 4C

mH2O @ 4C

ATM

inH2O @ 60F

d Factory setting.

Meaning

Inches of Water at 39.2 ° F (4 ° C) Inches of Water at 68 ° F (20 ° C) Millimeters of Mercury at 0° C (32 ° F) Pounds per Square Inch Kilopascals

Megapascals

Millibar

Bar

Grams per Square Centimeter Kilograms per Square Centimeter Inches of Mercury at 32 ° F (0 ° C) Millimeters of Water at 4° C (39.2 ° F) Meters of Water at 4 ° C (39.2 ° F) Normal Atmospheres

Inches of Water at 60 ° F (15.6 ° C)

* Static pressure may be absolute or gauge pressure, depending on the SMV model type.

Atmospheric Offset

For SMV models SMG170, (which uses gauge pressure as PV2 input), you must measure the absolute static pressure and then enter that value in the Atmospheric Offset field.

Continued on next page

1/99

SMV 3000 Transmitter User’s Manual

59

Page 71
Image 71
Honeywell SMV 3000 user manual AP/GPConf Configuration PV2, Absolute Pressure, STG170, Gauge Pressure, Atmospheric Offset