6.8 TempConf Configuration - PV3, Continued

ATTENTION

For a reverse range, enter the upper range value as the LRV and the lower range value as the URV. For example, to make a 0 to 500 °F range a reverse range, enter 500 as the LRV and 0 as the URV.

The URV changes automatically to compensate for any changes in the LRV and maintain the present span (URV – LRV). See Figure 23 for an example.

If you must change both the LRV and URV, always change the LRV first. However, if the change in the LRV would cause the URV to exceed the URL, you would have to change the URV to narrow the span before you could change the LRV

Figure 23 Example of LRV and URV Interaction

Current Range Settings

LRL

LRV

 

SPAN

 

URV

URL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-328

-100

257

 

600

842 oF

Range Settings After LRV is Changed to Zero (0)

LRL

 

LRV

 

SPAN

 

 

URV URL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-328

-100 0

257

600 700 842 oF