A.5 Configuration, Continued

ATTENTION

The actual engineering unit values available in a system will depend upon the LCN software release. See Section 10 in the PM/APM Smartline Transmitter Integration Manual for release dependent EU details.

DE_CONF Parameter While the DECONF selections are the same for all transmitters, the corresponding SCT 3000 selections for PV Type may differ. Table A-6 compares the PV Type selections for SMV 3000 with PED DECONF parameter selections for reference.

Table A-6 DECONF and PV Type Parameter Entry Comparison

IF PED DECONF entry is …

PV

PV_SV

PV_DB

PV_SV_DB

THEN comparable SCT 3000 PV Type entry can be any one of the following …

Not Applicable for SMV 3000.

Not Applicable for SMV 3000.

PV1,

PV1 and PV2,

PV1 - PV3, or

PV1 - PV4

PV1 w/SV1,

PV1 and PV2 w/SV1

PV1 - PV3 w/SV1, or

PV1 - PV4 w/SV1

URL Parameter

Table A-7 lists example Upper Range Limits for a given SMV 3000 transmitter PV. Remember that you can enter the desired URL for the PV4 range through the SCT 3000, but URL for PV1, PV2, and PV3 is a read only fixed value (determined by SMV model and process temperature sensor type).

Table A-7 Example URLs for a SMV Transmitter Model SMA125.

IF Process Variable Number is…

PV1

PV2

PV3

PV4

THEN URL is …

400inH2O

750psia

850° C (varies per sensor type) configurable

ATTENTION

If you leave the URL parameter blank, you can upload the transmitter database through the detail display commands to resolve the resulting database mismatch error. The URL is always part of the transmitter’s database.

Continued on next page

162

SMV 3000 Transmitter User’s Manual

1/99

Page 174
Image 174
Honeywell SMV 3000 user manual If PED Deconf entry is …, URL Parameter, Then URL is …