A.3 Data Exchange Functions, Continued

16 Points per STIMV IOP

The STIMV IOP contains sixteen AI points which are read/write accessible from the PMM and upper network components as shown in Figure A-3. Figure A-3 shows four SMV 3000 transmitters with four PVs each connected to IOP points 1, 5, 9 and 13, respectively.

You can mix single PV transmitters with multivariable transmitters within the given one to eight or nine to sixteen IOP boundary, but all PVs for a multivariable transmitter must be allotted to consecutive slots within a given IOP boundary. While a multivariable transmitter is physically connected to only one slot, the adjacent slots are allocated for the other PVs of the transmitter and they can not cross over or wrap around the IOP boundaries.

Note that points include the usual IOP PV processing parameters such as alarm limits, alarm hysteresis, PV clamping, and engineering unit conversion

Figure A-3 Sixteen AI Points per STIMV IOP

Universal

HM

Station

 

NIM

PM/APM/HPM

STIMV

PMM IOP

SMV 3000 Transmitters

with up to 4 PVs each

IOP handles 16 AI points split into boundaries of

8 slots each - 1 to 8 and 9 to 16

FTA

PVs allocated to

PVs allocated to

PVs allocated to

PVs allocated to

IOP slots 1 to 4.

IOP slots 5 to 8.

IOP slots 9 to 12.

IOP slots 13 to 16.