A.6 Operation Notes, Continued

Status Messages

Supplement the IOP status messages given in Section 8 of the PM/APM Smartline Transmitter Integration Manual with those listed in Table A-13. Note that the displayed status messages will be the same for all slots (PVs) associated with a given SMV 3000 transmitter.

Table A-13 Additional IOP Status Messages

Message

COMMAND ALLOWED ONLY ON FIRST SLOT OF MULTIPLE PV XMTRS

COMMAND FAILURE

. . . BUSY

CONFIGURATION MISMATCH MULTIPLE DEVICES ASSIGNED TO SLOT

TRANSMITTER IS

BROADCASTING A SUBSTITUTE VALUE PV

Problem

Attempted to download database with DECONF change from slot 2, 3, or 4.

Command could not be executed because transmitter is busy

Another transmitter is physically connected to a logical slot for a multivariable transmitter.

Transmitter is in output mode or input mode.

Corrective Action

Call up slot 1 Detail display for PV1 and retry database download command.

Retry command.

Disconnect offending transmitter or reconfigure the number of PVs for the SMV 3000 transmitter.

Use SCT 3000 to remove transmitter from output mode or input mode.

Bad PV Indication

In most cases, configuration error detection will result in a Bad PV (BP) indication for all slots (PVs) associated with a given SMV 3000 transmitter. However, if the number of IOP slots allocated differs from the number of PVs configured in the SMV 3000 transmitter, only the slots reserved by the IOP will be flagged as bad. A download command from slot 1 usually clears Bad PV indication from all but the offending slot (PV). You will have to make configuration changes to resolve slot conflicts.