A.5 Configuration, Continued

DAMPING Parameter The damping value is a real number selection from the transmitter range values shown in Table A-8 for a given SMV 3000 transmitter PV.

Table A-8 Damping Range Values for SMV 3000 Transmitter PVs

IF Process Variable Number is…

PV1 or PV2

PV3

PV4

THEN Damping Value can be …

0.00, 0.16, 0.32, 0.48, 1.0, 2.0, 4.0, 8.0, 16.0, or 32.0 seconds

0.00, 0.3, 0.7, 1.5, 3.1, 6.3, 12.7, 25.5, 51.1, or 102.3 seconds

0.00, 0.5, 1.0, 2.0, 3.0, 4.0, 5.0, 10.0, 50.0, or 100.0 seconds

ATTENTION

PIUOTDCF Parameter

CJTACT Parameter

The IOP may temporarily convert the entered damping value to a standard damping enumeration until it accesses the transmitter’s database.

This parameter represents the sensor fault detection ON/OFF selection for PV3 only.

This parameter will apply for PV3 thermocouple input only. It defines whether an internal cold-junction (ON) or an externally provided cold- junction reference (OFF) is to be used.

After Point is Built

Once you complete the point build for PV1, you can start building the point for the next PV or go to the Detail display for the point you just built and either upload the transmitter’s database to the IOP or download the IOP’s transmitter database to the transmitter. See Section A-6 in this Appendix and Section 7 in the PM/APM Smartline Transmitter Integration Manual for operation data using the Universal Station.

1/99

SMV 3000 Transmitter User’s Manual

163

Page 175
Image 175
Honeywell SMV 3000 user manual If Process Variable Number is… PV1 or PV2, Then Damping Value can be …, After Point is Built