6.8 TempConf Configuration - PV3

Engineering Units

The TempConf tab card displays the Low Range Value (LRV), Low Range Limit (LRL), Upper Range Value (URV) and Upper Range Limit (URL) for PV3 in the unit of measure selected in the Engineering Units field.

Selecting PV3 Engineering Units

Select one of the preprogrammed engineering units in Table 14 for display of the PV3 measurements, depending upon output characterization configuration.

Also select one of the preprogrammed engineering units for display of the cold junction temperature readings (CJT Units field). This selection is independent of the other sensor measurements. See Cold Junction Compensation on next page.

Table 14 Pre-programmed Engineering Units for PV3

Engineering Unit

Meaning

 

 

C d

Degrees Celsius or Centigrade

F

Degrees Fahrenheit

 

K

Kelvin

 

R

Degrees Rankine

 

 

 

NOTE: When output characterization configuration for PV3 is NON-LINEAR (see Output Characterization), PV3 input readings are displayed in the following units:

mV or V

milliVolts or Volts (for Thermocouple sensor)

Ohm

Ohms (for RTD sensor)

d Factory setting.

Continued on next page

1/99

SMV 3000 Transmitter User’s Manual

61

Page 73
Image 73