4.3Piping SMV 3000 Transmitter, Continued

Transmitter location

The suggested mounting location for the transmitter depends on the

 

process to be measured. Figure 11 shows the transmitter located above the

 

tap for gas flow measurement. This arrangement allows for condensate to

 

drain away from the transmitter.

 

Figure 12 shows the transmitter located below the tap for liquid or steam

 

flow measurement. This arrangement minimizes the static head effect of

 

the condensate. Although the transmitter can be located level with or

 

above the tap, this arrangement requires a siphon to protect the transmitter

 

from process steam. (The siphon retains water as a “fill fluid.”)

 

Figure 11 Transmitter Location Above Tap for Gas Flow Measurement

 

 

 

 

 

 

 

 

 

 

 

 

High

Pressure

Connection

Low

Pressure

Connection

3-Valve Manifold

To High

To Low

Pressure

Pressure

Connection

Connection

Continued on next page

1/99

SMV 3000 Transmitter User’s Manual

25