A.6 Operation Notes

Generic Operations

Detail Display

Difference

Most operator actions initiated through Detail displays at the Universal Station are generic for all Smartline transmitters. Refer to Section 7 in the PM/APM Smartline Transmitter Integration Manual for details about these generic operations.

This section outlines some differences in operations that are unique to the multivariable STIMV IOP and the SMV 3000 transmitter in particular.

Page 2 of the Detail display for a multivariable STIM point includes an additional field in the lower right hand corner for PV Number and Number of PVs identification as shown in Figure A-6. This lets you quickly identify what PV number you are viewing and how many PVs are associated with this given SMV 3000 transmitter.

Figure A-6 Detail Display with PV Number and Number of PVs Field.

 

 

 

 

23 Jun 98 11:15:23 6

F101 SMV SLOT 1 - DIFF PRESS 03 UNIT 01

CONFIG PAGE

_________________ CONFIGURATION DATA ________________

PVFORMAT

01

PVCHAR

 

LINEAR

PVLOPR

NOACTION

PVSRCOPT

ALL

SENSRTYP SPT_DP PVROCPPR NOACTION

PVCLAMP

CLAMP

PIUOTDCF

OFF

PVROCNPR NOACTION

PVALDR

ONE

BADPVPR

 

LOW

 

 

 

PVALDEBEU

2.0000

PVHHPR NOACTION

 

 

 

INPTDIR

REVERSE

PVHIPR NOACTION

 

 

 

LOCUTOFF

-------

PVLLPR NOACTION

 

 

 

______________ SMART TRANSMITTER DATA ______________

STITAG

FT3011

PVRAW

 

50.000

SECVAR

21.5762

SENSRTYP

SPT_DP

URL

400.000

DAMPING

0.00000

PVCHAR

LINEAR

URV

250.000

SERIALNO 10775120

CJTACT

OFF

LRV

0.00000

STISWVER

2.5

PIUOTDCF

OFF

LUL

0.00000

STATE

 

OK

DECONF

Pv_Sv_Db

STI_EU

 

INH2O

COMMAND

NONE

TRANSMITTER SCRATCH PAD:

 

 

 

 

 

TRANSMITTER STATUS

:

 

 

 

 

 

 

 

 

 

 

 

 

1 OF 1

PV Number

Number of PVs

Database Mismatch Parameters

The following parameters are added to the list of parameters that the STIMV IOP checks for database mismatches between itself and the transmitter.

PV Number

Number of PVs

Continued on next page