Lochinvar 1, 000 Primary/Secondary Boiler Piping, Minimum Boiler Water Temperatures, To System

Models: 000 through 2 1

1 80
Download 80 pages 59.46 Kb
Page 66
Image 66
PRIMARY/SECONDARY BOILER PIPING

PRIMARY/SECONDARY BOILER PIPING

TO SYSTEM

TO EXPANSION TANK

AND MAKEUP WATER SYSTEM

12” MAX.

FROM SYSTEM

FIG. 80 Primary/Secondary Piping of a Single Boiler

A properly sized primary system pump provides adequate flow to carry the heated boiler water to radiation, air over coils, etc. The fittings that connect the boiler to the primary system should be a maximum of 12" (0.30 m) (or 4 pipe diameters) apart to ensure connection at a point of zero pressure drop in the primary system. There should be 10 pipe diameters of straight pipe before and after the boiler secondary loop connections to prevent turbulent flow at the secondary loop connections. Multiple boilers may also be installed with a primary/secondary manifold system. Multiple boilers should be connected to the common manifold in reverse return to assist in balancing flow to multiple boilers.

The installer must ensure that the boiler has adequate flow without excessive temperature rise. Low system flow can result in overheating of the boiler water which can cause short burner cycles, system noise relief valve discharge and in extreme cases, a knocking flash to steam. These conditions indicate the need to increase boiler flow to and from the boiler. This is generally accomplished by increasing the diameter of the piping that connects the boiler to the primary system. A larger diameter pipe reduces head loss and increases flow.

CAUTION￿

At no time should the system pressure be less than 12 PSIG.

MAKE-UP WATER

FROM SYSTEM

CAP EACH MANIFOLD

TO SYSTEM

FIG. 81 Primary/Secondary Piping of Multiple Boilers

MINIMUM BOILER WATER

TEMPERATURES

Inlet water temperatures below the specified minimum recommendations can excessively cool the products of combustion resulting in condensation on the primary heat exchanger. The boiler is designed to condense only on the secondary heat exchanger. Condensation on the primary heat exchanger can cause operational problems, bad combustion, sooting, flue gas spillage and reduced service life of the related components.

66

Page 66
Image 66
Lochinvar 1, 000 through 2 Primary/Secondary Boiler Piping, Minimum Boiler Water Temperatures, To System To Expansion Tank