GAS SUPPLY

 

GAS PRESSURE TEST

 

 

 

Verify that the appliance is supplied with the type gas specified on the rating plate. Consult factory for installations at altitude.

INLET PRESSURE: Measured at the inlet pressure tap on the appliance gas manifold. The pressure tap is located upstream of the redundant gas valve and down stream of the field installed gas cock.

TABLE - K

Inlet Gas Pressure

 

 

Natural

 

L. P.

 

 

Gas

 

Gas

 

 

 

 

 

Max. (Inches-Water Column)

 

10.5" w.c.

 

13.0" w.c.

______________________________

 

________

 

_________

Min. (Inches-Water Column)

 

4.0" w.c.

 

4.0" w.c.

 

 

 

 

 

 

 

 

 

 

Maximum inlet gas pressure must not exceed the value specified. Minimum value listed is for the purposes of input adjustment.

MANIFOLD PRESSURE: Manifold pressure is a differential pressure measurement made between the high and low pressure taps at the gas orifice and the pressure in the transition chamber where the gas is supplied to the inlet of the combustion air blower. All manifold gas pressures are noted at full firing rate. The controls on this appliance may fire the burner from 25% up to 100% of rated input, based on system demand. Manifold gas pressure will be reduced as burner input is reduced. All reference gas pressure measurements must be made at 100% of rated burner input. The gas manifold pressure is pre-set at the factory by the ratio gas valve. Adjustment of manifold pressure is not normally required for proper operation. The adjustment point on the ratio gas valve is set at the factory. DO NOT attempt to adjust the settings on the ratio gas valve. Improper adjustment of the ratio gas valve may cause incomplete combustion or non-warrantable burner damage.

1.The appliance must be disconnected from the gas

supply

piping

system

during any

pressure

testing

of that

system

at a

test pressure

in excess

of 1/2

PSIG (3.5kPa).

 

 

 

 

2.The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply

piping system at test pressures equal to or less than 1/2 PSIG (3.5kPa).

3.The appliance and its gas connection must be leak-tested before placing it in operation.

GAS CONNECTION

1.Safe operation of unit requires properly sized gas supply piping. See gas line sizing data.

2.Gas pipe size may be larger than appliance connection.

3.Installation of a union at the appliance gas line connection is required for ease of service and removal of the gas train.

4. Install a manual main gas shutoff

valve,

outside

of

the appliance gas connection and

before

the

gas

valve, when local codes require.

 

 

 

5.A trap (drip leg) MUST be provided in the inlet of the gas connection to the appliance.

6.The diaphragm gas valve has a bleed port that requires venting to atmosphere, outside the building.

TABLE - L

Nominal Manifold Pressure

Settings at Full Fire

 

 

Natural

L. P.

Input Btu/hr

 

Gas

Gas

 

 

 

 

 

1,500,000 - 2,000,000

 

3.5" w.c.

 

3.5" w.c.

 

 

 

 

 

7.Optional gas controls may require routing of bleeds and vents to the atmosphere, outside the building when required by local codes.

23

Page 23
Image 23
Lochinvar 1, 000 through 2 warranty GAS Supply GAS Pressure Test, Table K, GAS Connection, Table L

000, 000 through 2, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.