Lochinvar 1, 000 Installation With A Chilled Water System, Boiler Operating Temperature Control

Models: 000 through 2 1

1 80
Download 80 pages 59.46 Kb
Page 69
Image 69
Boiler Operation

Boiler Operation

28.Turn the run/stop switch to the “RUN” position to start boiler operation.

29.Push the resets for low water level, high water temperature and flame failure.

30.Observe the boiler synchronization process before start-up of the boiler begins.

31.Boiler should begin the start-up process for the sequence of operation.

32.The boiler will fire at 50% of rated input on initial start-up and adjust input as required to meet system demand.

33.

The integral bypass valve will automatically

adjust

 

to maintain minimum inlet temperatures

to the

 

primary heat exchanger.

 

34.Ensure that inlet water temperature does not fall below the specified minimum for the boiler.

35.

Based on system demand, the

boiler may

run

for

 

an extended period of time at

a reduced

rate

of

 

input to maximize efficiency.

 

 

 

36.As system demand is satisfied, the burner will cycle off and the combustion air blower will run for a post purge operation before the boiler shuts down.

INSTALLATION WITH A

CHILLED WATER SYSTEM

EXPANSION

 

TANK

 

 

HEATING AND

 

COOLING COIL

GAS SUPPLY

PUMP

 

 

WATER

 

SUPPLY

 

CHILLER

FIG. 82 Installation with a Chilled Water System

Pipe refrigeration systems in parallel. Install duct coil downstream at the cooling coil. Where the hot water heating boiler is connected to a heating coil located in the air handling units which may be exposed to refrigeration air circulation, the boiler piping system must be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle. The coil must be vented at the high point and hot water from the boiler must enter the coil at this point. Due to the fast heating capacity of the boiler, it is not necessary to provide a ductstat to delay circulator operation. Also, omit thermostat flow checks as the boiler is cold when heating thermostat is satisfied. This provides greater economy over maintaining standby heat.

BOILER OPERATING

TEMPERATURE CONTROL

The operating temperature control for the boiler is the Excel 10 controller. It is located on the back side of the front control panel, behind the front access door. Access to adjust the temperature set point and other owner/operator adjustable points is made through the Command Display located on the front control panel. The sensing element for the operator is placed in a bulb well installed in the inlet connection to the boiler. The outlet sensor is located in a bulb well on the outlet side of the primary heat exchanger top header. Carefully observe the discharge water temperature on the initial boiler on cycles. The location of the temperature sensor may generally require a lower temperature set point on the operating control to achieve the desired discharge water temperature from the boiler. The return/inlet sensing element location allows a boiler to sustain longer burner on cycles.

The location of the operating sensor, inlet or outlet, is selectable from the screen on the Command Display.

The exact temperature set point is based on your system’s requirements. Set the control set point(s) to the desired operating water temperature. Observe the boiler discharge temperature after each set point adjustment to ensure proper operation.

The maximum set point for operation of a heating boiler is 220°F (104.4°C) on a standard Excel 10 control. The minimum temperature setting programmed into this standard Excel 10 control is 100°F (37.7°C).

69

Page 69
Image 69
Lochinvar 1, 000 warranty Installation With A Chilled Water System, Boiler Operating Temperature Control, Boiler Operation