OPERATION/DIAGNOSTIC

OPERATION/DIAGNOSTIC

LIGHTS, RESETS AND SWITCHES

ADJ

 

CIRCUIT

HI-LIMIT

BREAKER

 

 

 

ALARM

RESET

 

 

ALARM

POWER

 

 

SOUND

ALARM

 

SILENCE

 

 

LOW WATER CUT-OFF

AUTO RESET TEST

MANUAL

FIG. 66 Exterior Control Panel

The control panel has a lighted ON/OFF power switch and 11 indicating lights and switches to show operation, control sensed malfunctions and diagnostics.

BURNER

FIG. 67 Burner Assembly

 

 

TABLE - AA

 

 

Diagnostic Lights and Switches

 

Indicator

Function

 

 

 

 

Power

Lighted ON/OFF Main Power Switch.

_________________________________________________________________________________________________________

 

Alarm Silence

Rocker Switch to Silence an Optional Audible Alarm.

_________________________________________________________________________________________________________

 

Alarm Light

Amber Indicating Light for an Alarm Condition.

_________________________________________________________________________________________________________

 

High Limit Light

Red Indicating Light for Water Temperature Exceeding Maximum Setting of High Limit Control.

_________________________________________________________________________________________________________

 

High Limit Knob

Adjustable Rotary Knob to Set Maximum Water Temperature.

_________________________________________________________________________________________________________

 

High Limit Reset

Red Push Button to Reset High Limit when High Limit Setting is Exceeded.

_________________________________________________________________________________________________________

 

Circuit Breaker

Reset Button for a 5 Amp breaker on the 24 VAC Control Circuit.

_________________________________________________________________________________________________________

Low Water Cut-Off

_________________________________________________________________________________________________________

Test Switch Black Momentary Rocker Switch interrupts the sensing circuit of the Low Water Cut-Off to prove

 

operation.

_________________________________________________________________________________________________________

Reset Switch

Red Momentary Rocker Switch to Reset the Low Water Cut-Off after a test or Low Water Condition

when operating in the Manual Reset Mode.

_________________________________________________________________________________________________________

Command Display

_________________________________________________________________________________________________________

Run/Stop Switch “RUN” allows normal operation - “STOP” shuts down operation, but allows communication with a

network.

_________________________________________________________________________________________________________

Ignition Control

_________________________________________________________________________________________________________

Flame Failure Reset Red Push Button to reset the Hot Surface Ignition Control when a hard lockout condition from a Flame Failure has occurred.