Trane TRG-TRC011-EN manual Equipment Rating Standards

Page 64

period five

Application Considerations

notes

a refrigerant vapor detector to monitor refrigerant levels in the machinery room. When the detector measures refrigerant levels above those allowable, a building automation system is used to automatically shut down the combustion process. Due to the lower cost, many building owners employ exception (b) in machinery rooms that have direct-fired absorption chillers or boilers.

Establish definitions, testing, and rating requirements

Single- and double-effect absorption chillers

Indirect- and direct-fired absorption chillers

Water-and-lithium bromide solution

Figure 67

Equipment Rating Standards

The Air Conditioning & Refrigeration Institute (ARI) establishes rating standards for packaged HVAC equipment. The overall objective of ARI Standard 560 is to promote consistent rating of many types and sizes of absorption water chillers. It covers single-effect chillers operating on steam or a hot fluid, double-effect chillers operating on steam or a hot fluid, and direct-fired double-effect chillers operating on natural gas, oil, or liquid petroleum (LP). It pertains to chillers using water as the refrigerant and lithium bromide as the absorbent.

The standard rating conditions used for ARI rating represent typical design temperatures and flow rates for which water-cooled systems are designed. They are not suggestions for good design practice for a given system—they simply define a common rating point to aid comparisons. Trends toward improved system energy efficiency have changed some of the actual conditions for specific applications.

Impurities in the chilled- and cooling-water systems eventually deposit on evaporator, absorber, and condenser tube surfaces, impeding heat transfer. Catalogued performance data includes a fouling factor that accounts for this effect to more closely predict actual chiller performance.

Remember that the ARI rating is a standardized representation. Many chillers do not run at standard rating conditions. Performing a comprehensive energy analysis is still the best method of comparing the system operating cost difference between two chillers.

TRG-TRC011-EN

59

Image 64
Contents Air Conditioning Clinic Absorption Water Chillers Absorption Water Chillers Preface Contents TRG-TRC004-EN Introduction TRG-TRC011-EN Absorption Refrigeration Cycle Period onePeriod one Reject heat Heat energy Absorption System Fluids High affinity for water refrigerant Components of the Absorption Cycle Conditions Steam or Hot waterrefrigerant vapor Generator Condenser Refrigerant then flows into the evaporator pan Absorber spray pump Solution Heat Exchanger Dilute Generator pump Equilibrium Chart Heat Solution temperature Absorption Chiller Types Period twoSingle-Effect Chiller Absorber Evaporator spray pump Spray pump Generator pump Double-Effect Chiller Vapor Low Temperature condenser Cooling Generator Water Evaporator Absorber Low-temperature generator pump Generator pump Absorption Chiller Types Direct-Fired Chiller Evaporator High-temperature high-temperature Generatorgenerator pump Chiller/Heater Absorption Chiller Types Changeover Absorption Chiller Types Capacity Control Period threePeriod three Energy valve Generator Crystallization 10C 37.8C Capacity Control Capacity Control Capacity Control Heat exchanger bypass Evaporator pan Purge System Isolation valve Maintenance Considerations Period fourPeriod four Maintenance Considerations Test run with alternate fuel, if dual-fuel burner Maintenance Considerations Maintenance Considerations Corrosion inhibitor and performance additive recommendations Application Considerations Period fiveCooling-Water Temperature Limitations Combination Chiller Plants 58F Special Considerations for Direct-Fired Chillers Application Considerations Equipment Rating Standards Review Period sixPeriod six Review Review Review Quiz Questions for PeriodQuiz TRG-TRC011-EN Answers Glossary Glossary Glossary Trane Company