Trane TRG-TRC011-EN manual 58F

Page 61

period five

Application Considerations

notes

 

absorption

electric

 

chiller

chiller

58°F

 

 

[14.4°C]

50°F

42°F

 

 

[10°C]

[5.6°C]

Figure 64

The second beneficial operating characteristic is that an absorption chiller works more efficiently and produces more cooling with increased leaving- chilled-water temperatures.

Applications with two chillers can be either piped in series or in parallel. Though there are advantages associated with each arrangement, the series configuration allows a noticeable increase in the overall system efficiency of a combination gas-and-electric chiller plant. The series arrangement allows the upstream chiller to cool the water part of the way and uses the downstream chiller to cool the water the rest of the way to the setpoint. Placing the absorption chiller in the upstream position allows it to provide a warmer leaving-chilled-water temperature, 50ºF [10ºC] in this example. This not only improves the absorption chiller’s efficiency and capacity, but also reduces the cooling load and energy consumption of the electric chiller.

The series arrangement also has the capability to preferentially load the gas- burning chiller, allowing the system to maximize the use of lower-cost fuel during periods of high electrical energy cost. Piping two chillers in series also means that the entire system-water flow must pass through both chillers. Exercise care when selecting the chillers to avoid exceeding their maximum flow rates. Notice that the example series arrangement shown here also takes advantage of a 16°F [8.9°C] temperature differential across the chillers. This increased temperature differential allows the water flow rate to be reduced and results in lower pumping costs.

Overall, the key to successful implementation of a combination gas-and-electric chiller plant is an intelligent building automation system that optimizes chiller plant operation relative to electrical and gas utility rate structures.

56

TRG-TRC011-EN

Image 61
Contents Air Conditioning Clinic Absorption Water Chillers Absorption Water Chillers Preface Contents TRG-TRC004-EN Introduction TRG-TRC011-EN Period one Absorption Refrigeration CyclePeriod one Reject heat Heat energy Absorption System Fluids High affinity for water refrigerant Components of the Absorption Cycle Conditions Steam or Hot waterrefrigerant vapor Generator Condenser Refrigerant then flows into the evaporator pan Absorber spray pump Solution Heat Exchanger Dilute Generator pump Equilibrium Chart Heat Solution temperature Period two Absorption Chiller TypesSingle-Effect Chiller Absorber Evaporator spray pump Spray pump Generator pump Double-Effect Chiller Vapor Low Temperature condenser Cooling Generator Water Evaporator Absorber Low-temperature generator pump Generator pump Absorption Chiller Types Direct-Fired Chiller Evaporator High-temperature high-temperature Generatorgenerator pump Chiller/Heater Absorption Chiller Types Changeover Absorption Chiller Types Period three Capacity ControlPeriod three Energy valve Generator Crystallization 10C 37.8C Capacity Control Capacity Control Capacity Control Heat exchanger bypass Evaporator pan Purge System Isolation valve Period four Maintenance ConsiderationsPeriod four Maintenance Considerations Test run with alternate fuel, if dual-fuel burner Maintenance Considerations Maintenance Considerations Corrosion inhibitor and performance additive recommendations Period five Application ConsiderationsCooling-Water Temperature Limitations Combination Chiller Plants 58F Special Considerations for Direct-Fired Chillers Application Considerations Equipment Rating Standards Period six ReviewPeriod six Review Review Review Questions for Period QuizQuiz TRG-TRC011-EN Answers Glossary Glossary Glossary Trane Company