Trane TRG-TRC011-EN manual Capacity Control, Period three

Page 39

period three

Capacity Control

notes

period three

Figure 39

The primary objective of the chiller capacity control system is to reliably maintain the temperature of the chilled water leaving the evaporator. The control system monitors the temperature of the leaving chilled water, compares it to the setpoint, and adjusts the amount of solution supplied to the generator and the heat input to the generator.

15 psia

[103.4 kPa]

 

 

 

 

 

 

 

 

 

re

 

 

 

 

 

 

 

 

u

 

 

 

 

 

 

 

s

 

 

 

 

 

 

 

s

 

5 psia

 

 

 

 

 

re

 

 

 

 

 

 

p

 

 

 

 

 

 

 

r

 

 

 

 

 

 

 

o

 

 

 

 

 

[34.5 kPa]

 

p

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

v

 

 

 

 

 

 

 

 

 

1 psia

[6.9 kPa]

$

 

0 4

0 5

5 5

0 6

5 6

concentration

0.1 psia

&

 

%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[0.69 kPa]

 

 

 

 

 

 

 

50°F

 

100°F

 

 

150°F

200°F

LiBr solution

[10°C]

 

[37.8°C]

 

 

[65.6°C]

[93.3°C]

Figure 40

 

 

solution temperature

 

 

 

 

 

In Period One, the Equilibrium Chart for Aqueous Lithium Bromide Solutions was introduced to explain how the combination of solution temperature and concentration determines the pressure, and temperature, at which the refrigerant will boil (vaporize) in the evaporator. Recall that an increase in solution concentration ($ to %), at a constant temperature, results in a decrease in vapor pressure. Conversely, a decrease in solution temperature ($ to &), at a constant concentration, results in a decrease in vapor pressure. Assuming that no air or other noncondensables are inside the chiller, the vapor pressure of the solution determines the temperature at which the refrigerant will vaporize. In

34

TRG-TRC011-EN

Image 39
Contents Air Conditioning Clinic Absorption Water Chillers Absorption Water Chillers Preface Contents TRG-TRC004-EN Introduction TRG-TRC011-EN Period one Absorption Refrigeration CyclePeriod one Reject heat Heat energy Absorption System Fluids High affinity for water refrigerant Components of the Absorption Cycle Conditions Steam or Hot waterrefrigerant vapor Generator Condenser Refrigerant then flows into the evaporator pan Absorber spray pump Solution Heat Exchanger Dilute Generator pump Equilibrium Chart Heat Solution temperature Period two Absorption Chiller TypesSingle-Effect Chiller Absorber Evaporator spray pump Spray pump Generator pump Double-Effect Chiller Vapor Low Temperature condenser Cooling Generator Water Evaporator Absorber Low-temperature generator pump Generator pump Absorption Chiller Types Direct-Fired Chiller Evaporator High-temperature high-temperature Generatorgenerator pump Chiller/Heater Absorption Chiller Types Changeover Absorption Chiller Types Period three Capacity ControlPeriod three Energy valve Generator Crystallization 10C 37.8C Capacity Control Capacity Control Capacity Control Heat exchanger bypass Evaporator pan Purge System Isolation valve Period four Maintenance ConsiderationsPeriod four Maintenance Considerations Test run with alternate fuel, if dual-fuel burner Maintenance Considerations Maintenance Considerations Corrosion inhibitor and performance additive recommendations Period five Application ConsiderationsCooling-Water Temperature Limitations Combination Chiller Plants 58F Special Considerations for Direct-Fired Chillers Application Considerations Equipment Rating Standards Period six ReviewPeriod six Review Review Review Questions for Period QuizQuiz TRG-TRC011-EN Answers Glossary Glossary Glossary Trane Company