period three
Capacity Control
notes
other words, the combination of solution temperature and concentration determines the temperature at which the refrigerant will boil (vaporize).
Varying the temperature at which the refrigerant boils in the evaporator changes the capacity of the absorption water chiller. So, in order to control the capacity of the chiller to meet the
15 psia
[103.4 kPa]
|
|
|
|
|
|
|
|
| re |
|
|
|
|
|
|
|
| u | |
|
|
|
|
|
|
| s |
| |
|
|
|
|
|
| s |
| 5 psia | |
|
|
|
|
| re |
|
| ||
|
|
|
| p |
|
|
|
| |
|
|
| r |
|
|
|
|
| |
|
| o |
|
|
|
|
| [34.5 kPa] | |
| p |
|
|
|
|
|
| ||
a |
|
|
|
|
|
|
|
| |
v |
|
|
|
|
|
|
|
|
|
1 psia |
|
|
| & |
[6.9 kPa] |
|
| % | ' |
0.1 psia | $ | ) | ( |
|
[0.69 kPa] |
|
0
0 5
5 5
0
5 6
concentration
50°F | 100°F | 150°F | 200°F | LiBr solution |
[10°C] | [37.8°C] | [65.6°C] | [93.3°C] | Figure 41 |
| solution temperature |
| ||
|
|
|
A common method used to vary the temperature of the solution is to vary the amount of absorbent solution delivered to the generator. At part load, in response to a changing
Because less refrigerant is boiled off in the generator, the refrigerant flow rate through the cycle is decreased. Consequently, the heat rejected within the absorber is less. Less heat rejected by the cooling tower typically results in
Varying the solution flow to the generator can be accomplished in several ways. Historically, it has been common to use either a throttling valve or a bypass valve. A throttling valve creates an additional flow restriction in the pipe from the absorber to the generator, allowing the solution pump to ride up its pump curve, reducing the flow rate. A bypass valve diverts a portion of the solution back into the absorber, thus reducing the flow to the generator.
35 |