Fuse Replacement Data

Table 20 lists the replacement fuses for the control circuit, compressors, and condenser fans.

Table 20. Fuse Replacement Data

Fuse Replacement Selection

Fuse Description

Unit Size

Unit Voltage

Fuse Type

Fuse Size

 

 

 

 

 

Condenser Fan Fuse

 

200/230 VOLT

 

25 AMP

(1F1-1F3 on 20 - 30 Ton)

ALL

460/575 VOLT

CLASS K5

15 AMP

(1F1-1F6 on 20 - 60 Ton)

 

380/415 VOLT

 

 

 

 

 

 

 

 

 

Control CKT Fuse (1F7)

20 - 30 Ton

ALL

BUSSMANN S - 3.20

3.20 AMP

 

 

 

 

40 - 60 Ton

ALL

BUSSMANN S - 6.25

6.25 AMP

 

 

 

 

 

 

Compr Protector Fuse

 

 

 

 

(1F8 on 20 - 60 Ton)

ALL

ALL

BUSSMANN MTH - 6

6 AMP

(1F9 on 40 - 60 Ton)

 

 

 

 

 

 

 

 

 

Monthly Maintenance

Air Handling Equipment

Before completing the following checks, turn the system control circuit switch 1S2 and 5S1 to the "Off" position. Open the main power disconnect switch for the Condensing Unit and Air Handling Unit and "lock it" in the "Off" position before removing any access panels.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

[ ] Inspect the return air filters. Clean or replace them if necessary.

[ ] Check the evaporator drain pan and condensate piping to ensure that there are no blockages.

[ ] Inspect the evaporator coils for dirt. If the coils appear dirty, clean them according to the instructions described in the “Coil Cleaning” section.

[ ] Inspect the economizer damper hinges and pins (if applicable) to ensure that all moving parts are securely mounted. Clean the blades as necessary.

[ ] Verify that all damper linkages move freely; lubricate with white grease, if necessary.

[ ] Check Supply Fan motor bearings; repair or replace the motor as necessary.

[ ] Check the fan shaft bearings for wear. Replace the bearings as necessary.

[ ] Lubricate the supply fan bearings. Refer to the equipment manufacturer for their recommended greases.

NOTICE

Over lubrication can be just as harmful as not enough grease.

Use a hand grease gun to lubricate these bearings; add grease until a light bead appears all around the seal. Do not over lubricate!

After greasing the bearings, check the setscrews to ensure that the shaft is held securely to the bearings and Fan wheels. Make sure that all bearing supports are tight.

[ ] Check the supply fan belt(s). If the belts are frayed or worn, replace them.

106

SS-SVX09A-EN

Image 106
Contents Remote Split System Units JuneResponsible Refrigerant Practices Grounding RequiredEnvironmental Concerns Overview of ManualTable of Contents SS-SVX09A-EN Unit Nameplate Model Number DescriptionCompressor Nameplate Unit Description Unit Clearances Unit InspectionNo Step Surface EVP Chiller ConsiderationsInstallation Unit Dimensions & Weight InformationFoundation Installation RAUC-C20 Unit Dimensional Data & Recommended Clearances RAUC-C25 Unit Dimensional Data & Recommended Clearances RAUC-C30 Unit Dimensional Data & Recommended Clearances RAUC-C40 Unit Dimensional Data & Recommended Clearances RAUC-C50 Unit Dimensional Data & Recommended Clearances RAUC-C60 Unit Dimensional Data & Recommended Clearances Bphe 20 Evaporator Chiller Dimensions Bphe 25 Evaporator Chiller Dimensions Bphe 30 Evaporator Chiller Dimensions Bphe 40 Evaporator Chiller Dimensions Bphe 50 Evaporator Chiller Dimensions Bphe 60 Evaporator Chiller Dimensions Typical Unit Weights & Point Loading Data Typical EVP Chiller Weights & General DataRigging Heavy Objects Rigging and Center-of-Gravity DataNeoprene Isolators Unit IsolationTypical Neoprene Isolator Selection & Location Installation Spring Isolators Leveling the UnitTwo Manifolded Compressors Shipping FastenersCompressor Shipping Hardware Typical Spring Isolator Selection & LocationGeneral Unit Requirements Refrigerant Piping RequirementsHazard of Explosion Main Electrical Power Requirements Hazardous VoltageEVP Chilled Water Piping Requirements Volt Control Wiring All Units Ground WireField Installed Control Wiring Requirements No Controls UnitsEVP Chiller Piping Constant Volume Units Low Voltage Wiring AC & DC Hazardous VoltageVariable Air Volume VAV Units Refrigerant Line ComponentsLiquid Line Solenoid Valves Liquid Line Moisture Indicator Sight GlassAccess Valves Ports Thermostatic Expansion Valve TEVSolenoid Valve & Sight Glass w/Moisture Indicator Typical Placement of Split System piping ComponentsSuction Line Piping Suction Line Interconnecting TubingRefrigerant Piping Use Type L refrigerant grade copper tubing onlyLiquid Line Interconnecting Tubing Liquid Line PipingEvaporator Piping Typical Coil Piping For Dual Circuit UnitsOptional Pressure Gauges Hot Gas Bypass for Commercial Comfort-Cooling ApplicationsFinal Refrigerant Pipe Connections Brazing Procedures Hazard of Explosion and Deadly Gases Leak Testing Procedure Hazard of Explosion Chilled Water Piping Evaporator Water-Pressure Drop Water Temperature Sensor Installation Air VentsChiller Flow Switch Water Pressure GaugesFreezestat Typical Piping RecommendationsOptional Flow Switch Illustration Final Water Piping ConnectionsField Installed Power Wiring Disconnect Switch External Handle Factory Mounted OptionMain Unit Power Wiring Hazardous Voltage Equations Power Wire Sizing and Protection DeviceCustomer Connection Wire Range Calculation #1 MCA, MOP, and RDEInstallation Calculation #2 Disconnect Switch Sizing DSS Electrical Service Sizing DataField Installed Control Wiring Hazardous Voltage Controls Using 115 VAC Hazardous VoltageOutside Air Thermostat 5S57 EVP Interlocks EVP Flow control 6S58EVP Circulating Pump Interlock Hot Gas Bypass All control optionsControls using DC Analog Input/Outputs Hazardous Voltage Controls using 24 VAC Hazardous VoltageAC Conductors Economizer Actuator Circuit DC ConductorsNo System Control Temperature Control ParametersEconomizer Actuator Circuit Legend Refer to Wiring Notes on p Installation Variable Air Volume Control Honeywell W7100A Discharge Air Sensor Honeywell 6RT3Suction Line Thermostat Night Setback Hazardous VoltageEVP Chiller Control W7100G Discharge Chilled Water Controller Chilled Water Temperature Sensor Honeywell 6RT2 EVP Chiller Remote PanelOutside Air Thermostat 5S57 Field Provided Refer to Wiring Notes on Page p Electronic Zone Thermostat Honeywell T7067 Constant Volume Control HoneywellThermostat Wiring Thermostat CheckoutT7067 Electronic Zone Thermostat & Q667 Switching Subbase Q667 Switching Subbase Discharge Air Sensor Honeywell 6RT1Refer to Wiring Notes on Page p RT1 Discharge Air Sensor Assembly Compressor Damage EVP Chiller ApplicationsSystem Evacuation Procedures System Pre-Start ProceduresSystem Pre-Start Procedures Standing Vacuum Test Typical Vacuum Pump HookupEvacuation Time vs. Pressure Rise System Pre-Start Procedures W7100A Discharge Air Controller Economizer Actuator Checkout Zone or Discharge Air Temp ControllerOhms 4200 4000 3800 System Pre-Start Procedures W7100G Chilled Water Controller Master Energy Control Checkout Hazardous Voltage Zone Thermostat Checkout Honeywell T7067 Zone Thermostat 6U37 Voltage Output ramps TerminalsOhms Voltage Imbalance Electrical PhasingVAV W7100A Discharge Air Controller 7U11 Sequence of OperationEconomizer Cycle System Start-Up Chilled Water Temperature Controller 6U11Thermostatic Expansion Valve Condenser Fans W7100G Staging SequenceCompressor Crankcase Heaters Low Ambient DampersPump Down System Start-Up Low Ambient Thermostats Low Ambient Damper Adjustment Factory or Field InstalledLive Electrical Components Hot Gas Bypass OperationEVP Chiller Applications Freezestat Setting200 300 System Airflow Measurement Air Over Evaporator ApplicationRotating Components Verifying Proper Supply Fan RotationCompressor Start-Up All Systems Compressor Damage Live Electrical Components Measuring Subcooling SubcoolingMeasuring Superheat Compressor Oil Pressure Control Switch SettingsMinimum starting Ambient Temperature Recommended Refrigerant CapacitiesCompressor Sequence Typical Compressor Locations Ton Pressure Curve System Start-Up System Start-Up Ton Pressure Curve per Circuit 100 101 Final System Setup Recommended Operating SetpointsSample Maintenance Log At Shutdown Scroll Compressor ReplacementCompressor Operational Sounds At Low Ambient Start-UpService & Maintenance Compressor Circuit Breaker DataFuse Replacement Data Fuse Replacement DataMonthly Maintenance Air Handling EquipmentCoil Cleaning Condensing UnitHazardous Pressures System operationWarranty and Liability Clause Symbols NumericsIndex 111SS-SVX09A-EN

RAUC-C20, RAUC-C40, RAUC-C25, RAUC-C30, RAUC-C60 specifications

Trane, a leader in HVAC solutions, offers innovative air conditioning units designed for superior performance and energy efficiency. Among their advanced products are the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50, which cater to various cooling and heating needs in residential and commercial applications.

The RAUC-C series showcases cutting-edge technology, ensuring effective climate control while minimizing energy consumption. These units are equipped with variable-speed compressors, allowing for precise cooling capacities and reduced noise levels during operation. This feature ensures that users can enjoy optimal comfort without the disruptive noise often associated with traditional HVAC systems.

One of the standout technologies used in the RAUC-C series is Trane’s advanced inverter technology. This system intelligently adjusts the compressor speed based on real-time cooling demands, enhancing efficiency and prolonging the unit's lifespan. Additionally, the units come with high SEER (Seasonal Energy Efficiency Ratio) ratings, making them an excellent choice for those looking to lower their energy bills while maintaining a comfortable indoor environment.

The RAUC-C series units are designed with durability in mind. Constructed with robust materials, these air conditioning systems are built to withstand varying weather conditions. Their compact and lightweight design makes installation straightforward, and they can fit seamlessly into a variety of spaces, from residential homes to commercial buildings.

Another key characteristic of the RAUC-C series is their eco-friendly refrigerant, which meets strict environmental regulations. This not only supports sustainability efforts but also ensures efficient cooling performance. Furthermore, their smart technology capabilities enable integration with modern smart home systems, allowing users to manage their cooling settings remotely for added convenience.

Trane's focus on user-friendly interfaces makes these units easy to operate. The intuitive control systems allow users to customize their cooling preferences easily, providing flexibility to adapt to individual comfort needs.

Overall, the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50 stand out for their energy efficiency, advanced technology, durability, and user-focused design. These features make them reliable choices for anyone seeking efficient and effective heating and cooling solutions.