Trane RAUC-C60, RAUC-C50, RAUC-C30, RAUC-C20, RAUC-C40 Compressor Damage, EVP Chiller Applications

Page 68

System Pre-Start Procedures

Use the checklist provided below in conjunction with the “General Unit Requirement” checklist” to ensure that the unit is properly installed and ready for operation. Be sure to complete all of the procedures described in this section before starting the unit for the first time.

WARNING

Hazardous Voltage!

Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.

[ ] Turn the field supplied disconnect switch, located upstream of the unit, to the “Off” position.

[ ] Turn the “System” selection switch (at the Remote Panel) to the “Off” position and the “Fan” selection switch (if applicable) to the “Auto” or “Off” position.

[ ] Check all electrical connections for tightness and “point of termination” accuracy.

[ ] Verify that the condenser airflow will be unobstructed.

[ ] Check the condenser fan blades. Ensure they rotate freely within the fan orifices and are securely fastened to the fan motor shaft.

[ ] Disable the compressor (s) by unplugging the reset relay for each circuit. Refer to the unit-wiring diagram that sipped with the unit.

NOTICE

Compressor Damage!

Do not allow liquid refrigerant to enter the suction line. Excessive liquid accumulation in the liquid lines could result in compressor damage.

[ ] Verify that all compressor service valves, discharge service valves, and liquid line service valves is back seated on each circuit.

COMPRESSOR SERVICE VALVES MUST BE FULLY OPENED BEFORE START-UP (SUCTION, DISCHARGE, LIQUID LINE, AND OIL LINE).

[ ] Remove the protective plastic coverings that shipped over the compressors.

[ ] Check the compressor oil levels. The oil level in each manifold set of compressor sight glasses should be equally 1/2 to 3/4 full when they are “Off”.

[ ] Pack Stock Units;

Two low pressure switches are installed at the factory. However, only one is wired into the control circuit. This is to facilitate either an EVP chiller application or an air over evaporator application. Before starting the system, verify that the correct pressure switch for the application is connected to the control circuit. Refer to Table 13 for the pressure control settings and the unit wiring diagram, that shipped with the unit, for the appropriate connections.

[ ] Check the condenser coils. They should be clean and the fins should be straight. Straighten any bent coil fins with an appropriate sized fin comb.

[ ] Inspect the interior of the unit for tools and debris.

EVP Chiller Applications

[ ] Fill the chilled water system.

[ ] Vent the chilled water system at the highest points in the system. Brazed plate heat exchangers should be purged with water through the field provided vent ports to displace any air in the heat exchanger. Shell and tube heat exchanges (chiller barrels) should have the vent plug removed

68

SS-SVX09A-EN

Image 68
Contents Remote Split System Units JuneGrounding Required Environmental ConcernsResponsible Refrigerant Practices Overview of ManualTable of Contents SS-SVX09A-EN Compressor Nameplate Model Number DescriptionUnit Nameplate Unit Description Unit Inspection No Step SurfaceUnit Clearances EVP Chiller ConsiderationsFoundation Unit Dimensions & Weight InformationInstallation Installation RAUC-C20 Unit Dimensional Data & Recommended Clearances RAUC-C25 Unit Dimensional Data & Recommended Clearances RAUC-C30 Unit Dimensional Data & Recommended Clearances RAUC-C40 Unit Dimensional Data & Recommended Clearances RAUC-C50 Unit Dimensional Data & Recommended Clearances RAUC-C60 Unit Dimensional Data & Recommended Clearances Bphe 20 Evaporator Chiller Dimensions Bphe 25 Evaporator Chiller Dimensions Bphe 30 Evaporator Chiller Dimensions Bphe 40 Evaporator Chiller Dimensions Bphe 50 Evaporator Chiller Dimensions Bphe 60 Evaporator Chiller Dimensions Typical Unit Weights & Point Loading Data Typical EVP Chiller Weights & General DataRigging Heavy Objects Rigging and Center-of-Gravity DataTypical Neoprene Isolator Selection & Location Unit IsolationNeoprene Isolators Installation Spring Isolators Leveling the UnitShipping Fasteners Compressor Shipping HardwareTwo Manifolded Compressors Typical Spring Isolator Selection & LocationGeneral Unit Requirements Refrigerant Piping RequirementsEVP Chilled Water Piping Requirements Main Electrical Power Requirements Hazardous VoltageHazard of Explosion Ground Wire Field Installed Control Wiring RequirementsVolt Control Wiring All Units No Controls UnitsEVP Chiller Piping Low Voltage Wiring AC & DC Hazardous Voltage Variable Air Volume VAV UnitsConstant Volume Units Refrigerant Line ComponentsLiquid Line Moisture Indicator Sight Glass Access Valves PortsLiquid Line Solenoid Valves Thermostatic Expansion Valve TEVSolenoid Valve & Sight Glass w/Moisture Indicator Typical Placement of Split System piping ComponentsSuction Line Interconnecting Tubing Refrigerant PipingSuction Line Piping Use Type L refrigerant grade copper tubing onlyLiquid Line Interconnecting Tubing Liquid Line PipingEvaporator Piping Typical Coil Piping For Dual Circuit UnitsFinal Refrigerant Pipe Connections Hot Gas Bypass for Commercial Comfort-Cooling ApplicationsOptional Pressure Gauges Brazing Procedures Hazard of Explosion and Deadly Gases Leak Testing Procedure Hazard of Explosion Chilled Water Piping Evaporator Water-Pressure Drop Installation Air Vents Chiller Flow SwitchWater Temperature Sensor Water Pressure GaugesFreezestat Typical Piping RecommendationsOptional Flow Switch Illustration Final Water Piping ConnectionsField Installed Power Wiring Disconnect Switch External Handle Factory Mounted OptionMain Unit Power Wiring Hazardous Voltage Power Wire Sizing and Protection Device Customer Connection Wire RangeEquations Calculation #1 MCA, MOP, and RDEInstallation Calculation #2 Disconnect Switch Sizing DSS Electrical Service Sizing DataField Installed Control Wiring Hazardous Voltage Controls Using 115 VAC Hazardous VoltageEVP Interlocks EVP Flow control 6S58 EVP Circulating Pump InterlockOutside Air Thermostat 5S57 Hot Gas Bypass All control optionsAC Conductors Controls using 24 VAC Hazardous VoltageControls using DC Analog Input/Outputs Hazardous Voltage Economizer Actuator Circuit DC ConductorsEconomizer Actuator Circuit Legend Temperature Control ParametersNo System Control Refer to Wiring Notes on p Installation Variable Air Volume Control Honeywell W7100A Discharge Air Sensor Honeywell 6RT3Suction Line Thermostat Night Setback Hazardous VoltageEVP Chiller Control W7100G Discharge Chilled Water Controller Chilled Water Temperature Sensor Honeywell 6RT2 EVP Chiller Remote PanelOutside Air Thermostat 5S57 Field Provided Refer to Wiring Notes on Page p Constant Volume Control Honeywell Thermostat WiringElectronic Zone Thermostat Honeywell T7067 Thermostat CheckoutT7067 Electronic Zone Thermostat & Q667 Switching Subbase Q667 Switching Subbase Discharge Air Sensor Honeywell 6RT1Refer to Wiring Notes on Page p RT1 Discharge Air Sensor Assembly Compressor Damage EVP Chiller ApplicationsSystem Evacuation Procedures System Pre-Start ProceduresSystem Pre-Start Procedures Standing Vacuum Test Typical Vacuum Pump HookupEvacuation Time vs. Pressure Rise System Pre-Start Procedures W7100A Discharge Air Controller Economizer Actuator Checkout Zone or Discharge Air Temp ControllerOhms 4200 4000 3800 System Pre-Start Procedures W7100G Chilled Water Controller Master Energy Control Checkout Hazardous Voltage Zone Thermostat Checkout Honeywell T7067 Zone Thermostat 6U37 Voltage Output ramps TerminalsOhms Voltage Imbalance Electrical PhasingEconomizer Cycle Sequence of OperationVAV W7100A Discharge Air Controller 7U11 Thermostatic Expansion Valve Chilled Water Temperature Controller 6U11System Start-Up Condenser Fans W7100G Staging SequencePump Down Low Ambient DampersCompressor Crankcase Heaters Low Ambient Damper Adjustment Factory or Field Installed Live Electrical ComponentsSystem Start-Up Low Ambient Thermostats Hot Gas Bypass Operation200 300 Freezestat SettingEVP Chiller Applications Air Over Evaporator Application Rotating ComponentsSystem Airflow Measurement Verifying Proper Supply Fan RotationCompressor Start-Up All Systems Compressor Damage Live Electrical Components Measuring Superheat SubcoolingMeasuring Subcooling Pressure Control Switch Settings Minimum starting Ambient TemperatureCompressor Oil Recommended Refrigerant CapacitiesCompressor Sequence Typical Compressor Locations Ton Pressure Curve System Start-Up System Start-Up Ton Pressure Curve per Circuit 100 101 Final System Setup Recommended Operating SetpointsSample Maintenance Log Scroll Compressor Replacement Compressor Operational SoundsAt Shutdown At Low Ambient Start-UpService & Maintenance Compressor Circuit Breaker DataFuse Replacement Data Monthly MaintenanceFuse Replacement Data Air Handling EquipmentCoil Cleaning Condensing UnitHazardous Pressures System operationWarranty and Liability Clause Symbols NumericsIndex 111SS-SVX09A-EN

RAUC-C20, RAUC-C40, RAUC-C25, RAUC-C30, RAUC-C60 specifications

Trane, a leader in HVAC solutions, offers innovative air conditioning units designed for superior performance and energy efficiency. Among their advanced products are the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50, which cater to various cooling and heating needs in residential and commercial applications.

The RAUC-C series showcases cutting-edge technology, ensuring effective climate control while minimizing energy consumption. These units are equipped with variable-speed compressors, allowing for precise cooling capacities and reduced noise levels during operation. This feature ensures that users can enjoy optimal comfort without the disruptive noise often associated with traditional HVAC systems.

One of the standout technologies used in the RAUC-C series is Trane’s advanced inverter technology. This system intelligently adjusts the compressor speed based on real-time cooling demands, enhancing efficiency and prolonging the unit's lifespan. Additionally, the units come with high SEER (Seasonal Energy Efficiency Ratio) ratings, making them an excellent choice for those looking to lower their energy bills while maintaining a comfortable indoor environment.

The RAUC-C series units are designed with durability in mind. Constructed with robust materials, these air conditioning systems are built to withstand varying weather conditions. Their compact and lightweight design makes installation straightforward, and they can fit seamlessly into a variety of spaces, from residential homes to commercial buildings.

Another key characteristic of the RAUC-C series is their eco-friendly refrigerant, which meets strict environmental regulations. This not only supports sustainability efforts but also ensures efficient cooling performance. Furthermore, their smart technology capabilities enable integration with modern smart home systems, allowing users to manage their cooling settings remotely for added convenience.

Trane's focus on user-friendly interfaces makes these units easy to operate. The intuitive control systems allow users to customize their cooling preferences easily, providing flexibility to adapt to individual comfort needs.

Overall, the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50 stand out for their energy efficiency, advanced technology, durability, and user-focused design. These features make them reliable choices for anyone seeking efficient and effective heating and cooling solutions.