Trane RAUC-C60, RAUC-C50, RAUC-C30 manual Brazing Procedures Hazard of Explosion and Deadly Gases

Page 38

Installation

Brazing Procedures

WARNING

Hazard of Explosion and Deadly Gases!

Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant handling practices could result in death or serious injury.

Proper brazing techniques are essential when installing refrigerant piping. The following factors should be kept in mind when forming sweat connections.

WARNING

Hazard of Explosion!

Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant, when used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property-only damage.

1.When copper is heated in the presence of air, Copper oxide forms. To prevent copper oxide from forming inside the tubing during brazing, sweep an inert gas, such as dry nitrogen, through the tubing. Nitrogen displaces air in the tubing and prevents oxidation of the interior surfaces. A nitrogen flow of one to three cubic feet per minute is sufficient to displace the air. Use a pressure regulating valve or flow meter to control the flow.

2.Ensure that the tubing surfaces to be brazed are clean, and that the ends of the tubes have been carefully reamed to remove any burrs.

3.Make sure the inner and outer tubes of the joint are symmetrical and have a close clearance, providing an easy slip fit. If the joint is too loose, the tensile strength of the connection will be significantly reduced. The overlap distance should be equal to the diameter of the inner tube.

4.Wrap the body of each refrigerant line component with a wet cloth to keep it cool during brazing. Move any tube entrance grommets away for the brazing area.

Note: Use 40 to 45% silver brazing alloy (BAg-7 or BAg-28) on dissimilar metals. Use BCup-6 brazing alloy on copper to copper joints.

5.If flux is used, apply it sparingly to the joint. Excessive flux can enter the system which will contaminate the refrigerant system.

6.Apply heat evenly over the length and circumference of the joint to draw the brazing material into the joint by capillary action. Remove the brazing rod and flame from the joint as soon as a complete fillet is formed to avoid possible restriction in the line.

7.Visually inspect the connection after brazing to locate any pin holes or crevices in the joint. The use of a mirror may be required, depending on the joint location.

38

SS-SVX09A-EN

Image 38
Contents Remote Split System Units JuneResponsible Refrigerant Practices Grounding RequiredEnvironmental Concerns Overview of ManualTable of Contents SS-SVX09A-EN Compressor Nameplate Model Number DescriptionUnit Nameplate Unit Description Unit Clearances Unit InspectionNo Step Surface EVP Chiller ConsiderationsFoundation Unit Dimensions & Weight InformationInstallation Installation RAUC-C20 Unit Dimensional Data & Recommended Clearances RAUC-C25 Unit Dimensional Data & Recommended Clearances RAUC-C30 Unit Dimensional Data & Recommended Clearances RAUC-C40 Unit Dimensional Data & Recommended Clearances RAUC-C50 Unit Dimensional Data & Recommended Clearances RAUC-C60 Unit Dimensional Data & Recommended Clearances Bphe 20 Evaporator Chiller Dimensions Bphe 25 Evaporator Chiller Dimensions Bphe 30 Evaporator Chiller Dimensions Bphe 40 Evaporator Chiller Dimensions Bphe 50 Evaporator Chiller Dimensions Bphe 60 Evaporator Chiller Dimensions Typical Unit Weights & Point Loading Data Typical EVP Chiller Weights & General DataRigging Heavy Objects Rigging and Center-of-Gravity DataTypical Neoprene Isolator Selection & Location Unit IsolationNeoprene Isolators Installation Spring Isolators Leveling the UnitTwo Manifolded Compressors Shipping FastenersCompressor Shipping Hardware Typical Spring Isolator Selection & LocationGeneral Unit Requirements Refrigerant Piping RequirementsEVP Chilled Water Piping Requirements Main Electrical Power Requirements Hazardous VoltageHazard of Explosion Volt Control Wiring All Units Ground WireField Installed Control Wiring Requirements No Controls UnitsEVP Chiller Piping Constant Volume Units Low Voltage Wiring AC & DC Hazardous VoltageVariable Air Volume VAV Units Refrigerant Line ComponentsLiquid Line Solenoid Valves Liquid Line Moisture Indicator Sight GlassAccess Valves Ports Thermostatic Expansion Valve TEVSolenoid Valve & Sight Glass w/Moisture Indicator Typical Placement of Split System piping ComponentsSuction Line Piping Suction Line Interconnecting TubingRefrigerant Piping Use Type L refrigerant grade copper tubing onlyLiquid Line Interconnecting Tubing Liquid Line PipingEvaporator Piping Typical Coil Piping For Dual Circuit UnitsFinal Refrigerant Pipe Connections Hot Gas Bypass for Commercial Comfort-Cooling ApplicationsOptional Pressure Gauges Brazing Procedures Hazard of Explosion and Deadly Gases Leak Testing Procedure Hazard of Explosion Chilled Water Piping Evaporator Water-Pressure Drop Water Temperature Sensor Installation Air VentsChiller Flow Switch Water Pressure GaugesFreezestat Typical Piping RecommendationsOptional Flow Switch Illustration Final Water Piping ConnectionsField Installed Power Wiring Disconnect Switch External Handle Factory Mounted OptionMain Unit Power Wiring Hazardous Voltage Equations Power Wire Sizing and Protection DeviceCustomer Connection Wire Range Calculation #1 MCA, MOP, and RDEInstallation Calculation #2 Disconnect Switch Sizing DSS Electrical Service Sizing DataField Installed Control Wiring Hazardous Voltage Controls Using 115 VAC Hazardous VoltageOutside Air Thermostat 5S57 EVP Interlocks EVP Flow control 6S58EVP Circulating Pump Interlock Hot Gas Bypass All control optionsAC Conductors Controls using 24 VAC Hazardous VoltageControls using DC Analog Input/Outputs Hazardous Voltage Economizer Actuator Circuit DC ConductorsEconomizer Actuator Circuit Legend Temperature Control ParametersNo System Control Refer to Wiring Notes on p Installation Variable Air Volume Control Honeywell W7100A Discharge Air Sensor Honeywell 6RT3Suction Line Thermostat Night Setback Hazardous VoltageEVP Chiller Control W7100G Discharge Chilled Water Controller Chilled Water Temperature Sensor Honeywell 6RT2 EVP Chiller Remote PanelOutside Air Thermostat 5S57 Field Provided Refer to Wiring Notes on Page p Electronic Zone Thermostat Honeywell T7067 Constant Volume Control HoneywellThermostat Wiring Thermostat CheckoutT7067 Electronic Zone Thermostat & Q667 Switching Subbase Q667 Switching Subbase Discharge Air Sensor Honeywell 6RT1Refer to Wiring Notes on Page p RT1 Discharge Air Sensor Assembly Compressor Damage EVP Chiller ApplicationsSystem Evacuation Procedures System Pre-Start ProceduresSystem Pre-Start Procedures Standing Vacuum Test Typical Vacuum Pump HookupEvacuation Time vs. Pressure Rise System Pre-Start Procedures W7100A Discharge Air Controller Economizer Actuator Checkout Zone or Discharge Air Temp ControllerOhms 4200 4000 3800 System Pre-Start Procedures W7100G Chilled Water Controller Master Energy Control Checkout Hazardous Voltage Zone Thermostat Checkout Honeywell T7067 Zone Thermostat 6U37 Voltage Output ramps TerminalsOhms Voltage Imbalance Electrical PhasingEconomizer Cycle Sequence of OperationVAV W7100A Discharge Air Controller 7U11 Thermostatic Expansion Valve Chilled Water Temperature Controller 6U11System Start-Up Condenser Fans W7100G Staging SequencePump Down Low Ambient DampersCompressor Crankcase Heaters System Start-Up Low Ambient Thermostats Low Ambient Damper Adjustment Factory or Field InstalledLive Electrical Components Hot Gas Bypass Operation200 300 Freezestat SettingEVP Chiller Applications System Airflow Measurement Air Over Evaporator ApplicationRotating Components Verifying Proper Supply Fan RotationCompressor Start-Up All Systems Compressor Damage Live Electrical Components Measuring Superheat SubcoolingMeasuring Subcooling Compressor Oil Pressure Control Switch SettingsMinimum starting Ambient Temperature Recommended Refrigerant CapacitiesCompressor Sequence Typical Compressor Locations Ton Pressure Curve System Start-Up System Start-Up Ton Pressure Curve per Circuit 100 101 Final System Setup Recommended Operating SetpointsSample Maintenance Log At Shutdown Scroll Compressor ReplacementCompressor Operational Sounds At Low Ambient Start-UpService & Maintenance Compressor Circuit Breaker DataFuse Replacement Data Fuse Replacement DataMonthly Maintenance Air Handling EquipmentCoil Cleaning Condensing UnitHazardous Pressures System operationWarranty and Liability Clause Symbols NumericsIndex 111SS-SVX09A-EN

RAUC-C20, RAUC-C40, RAUC-C25, RAUC-C30, RAUC-C60 specifications

Trane, a leader in HVAC solutions, offers innovative air conditioning units designed for superior performance and energy efficiency. Among their advanced products are the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50, which cater to various cooling and heating needs in residential and commercial applications.

The RAUC-C series showcases cutting-edge technology, ensuring effective climate control while minimizing energy consumption. These units are equipped with variable-speed compressors, allowing for precise cooling capacities and reduced noise levels during operation. This feature ensures that users can enjoy optimal comfort without the disruptive noise often associated with traditional HVAC systems.

One of the standout technologies used in the RAUC-C series is Trane’s advanced inverter technology. This system intelligently adjusts the compressor speed based on real-time cooling demands, enhancing efficiency and prolonging the unit's lifespan. Additionally, the units come with high SEER (Seasonal Energy Efficiency Ratio) ratings, making them an excellent choice for those looking to lower their energy bills while maintaining a comfortable indoor environment.

The RAUC-C series units are designed with durability in mind. Constructed with robust materials, these air conditioning systems are built to withstand varying weather conditions. Their compact and lightweight design makes installation straightforward, and they can fit seamlessly into a variety of spaces, from residential homes to commercial buildings.

Another key characteristic of the RAUC-C series is their eco-friendly refrigerant, which meets strict environmental regulations. This not only supports sustainability efforts but also ensures efficient cooling performance. Furthermore, their smart technology capabilities enable integration with modern smart home systems, allowing users to manage their cooling settings remotely for added convenience.

Trane's focus on user-friendly interfaces makes these units easy to operate. The intuitive control systems allow users to customize their cooling preferences easily, providing flexibility to adapt to individual comfort needs.

Overall, the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50 stand out for their energy efficiency, advanced technology, durability, and user-focused design. These features make them reliable choices for anyone seeking efficient and effective heating and cooling solutions.