System Pre-Start Procedures

Note: It is unlawful to release refrigerant into the atmosphere. When service procedures require working with refrigerants, the service technician must comply with all Federal, State, and local laws. Refer to the General Service Bulletin MSCU-SB-1 (latest edition).

Standing Vacuum Test

Once 300 microns or less is obtained, close Valve A and leave valves B and C open. This will allow the vacuum gauge to read the actual system pressure. Let the system equalize for approximately 15 minutes. This is referred to as a “standing vacuum test” where, time versus pressure rise. The maximum allowable rise over a 15 minute period is 200 microns. If the pressure rise is greater than 200 microns but levels off to a constant value, excessive moisture is present. If the pressure steadily continues to rise, a leak is indicated. Figure 35 illustrates three possible results of the “standing vacuum test”. If a leak is encounter, repair the system and repeat the evacuation process until the recommended vacuum is obtained. Once the system has been evacuated, break the vacuum with refrigerant, and complete the remaining “Pre-Start Procedures” before starting the unit.

Figure 34. Typical Vacuum Pump Hookup

70

SS-SVX09A-EN

Image 70
Contents Remote Split System Units JuneResponsible Refrigerant Practices Grounding RequiredEnvironmental Concerns Overview of ManualTable of Contents SS-SVX09A-EN Unit Nameplate Model Number DescriptionCompressor Nameplate Unit Description Unit Clearances Unit InspectionNo Step Surface EVP Chiller ConsiderationsInstallation Unit Dimensions & Weight InformationFoundation Installation RAUC-C20 Unit Dimensional Data & Recommended Clearances RAUC-C25 Unit Dimensional Data & Recommended Clearances RAUC-C30 Unit Dimensional Data & Recommended Clearances RAUC-C40 Unit Dimensional Data & Recommended Clearances RAUC-C50 Unit Dimensional Data & Recommended Clearances RAUC-C60 Unit Dimensional Data & Recommended Clearances Bphe 20 Evaporator Chiller Dimensions Bphe 25 Evaporator Chiller Dimensions Bphe 30 Evaporator Chiller Dimensions Bphe 40 Evaporator Chiller Dimensions Bphe 50 Evaporator Chiller Dimensions Bphe 60 Evaporator Chiller Dimensions Typical Unit Weights & Point Loading Data Typical EVP Chiller Weights & General DataRigging Heavy Objects Rigging and Center-of-Gravity DataNeoprene Isolators Unit IsolationTypical Neoprene Isolator Selection & Location Installation Spring Isolators Leveling the UnitTwo Manifolded Compressors Shipping FastenersCompressor Shipping Hardware Typical Spring Isolator Selection & LocationGeneral Unit Requirements Refrigerant Piping RequirementsHazard of Explosion Main Electrical Power Requirements Hazardous VoltageEVP Chilled Water Piping Requirements Volt Control Wiring All Units Ground WireField Installed Control Wiring Requirements No Controls UnitsEVP Chiller Piping Constant Volume Units Low Voltage Wiring AC & DC Hazardous VoltageVariable Air Volume VAV Units Refrigerant Line ComponentsLiquid Line Solenoid Valves Liquid Line Moisture Indicator Sight GlassAccess Valves Ports Thermostatic Expansion Valve TEVSolenoid Valve & Sight Glass w/Moisture Indicator Typical Placement of Split System piping ComponentsSuction Line Piping Suction Line Interconnecting TubingRefrigerant Piping Use Type L refrigerant grade copper tubing onlyLiquid Line Interconnecting Tubing Liquid Line PipingEvaporator Piping Typical Coil Piping For Dual Circuit UnitsOptional Pressure Gauges Hot Gas Bypass for Commercial Comfort-Cooling ApplicationsFinal Refrigerant Pipe Connections Brazing Procedures Hazard of Explosion and Deadly Gases Leak Testing Procedure Hazard of Explosion Chilled Water Piping Evaporator Water-Pressure Drop Water Temperature Sensor Installation Air VentsChiller Flow Switch Water Pressure GaugesFreezestat Typical Piping RecommendationsOptional Flow Switch Illustration Final Water Piping ConnectionsField Installed Power Wiring Disconnect Switch External Handle Factory Mounted OptionMain Unit Power Wiring Hazardous Voltage Equations Power Wire Sizing and Protection DeviceCustomer Connection Wire Range Calculation #1 MCA, MOP, and RDEInstallation Calculation #2 Disconnect Switch Sizing DSS Electrical Service Sizing DataField Installed Control Wiring Hazardous Voltage Controls Using 115 VAC Hazardous VoltageOutside Air Thermostat 5S57 EVP Interlocks EVP Flow control 6S58EVP Circulating Pump Interlock Hot Gas Bypass All control optionsControls using DC Analog Input/Outputs Hazardous Voltage Controls using 24 VAC Hazardous VoltageAC Conductors Economizer Actuator Circuit DC ConductorsNo System Control Temperature Control ParametersEconomizer Actuator Circuit Legend Refer to Wiring Notes on p Installation Variable Air Volume Control Honeywell W7100A Discharge Air Sensor Honeywell 6RT3Suction Line Thermostat Night Setback Hazardous VoltageEVP Chiller Control W7100G Discharge Chilled Water Controller Chilled Water Temperature Sensor Honeywell 6RT2 EVP Chiller Remote PanelOutside Air Thermostat 5S57 Field Provided Refer to Wiring Notes on Page p Electronic Zone Thermostat Honeywell T7067 Constant Volume Control HoneywellThermostat Wiring Thermostat CheckoutT7067 Electronic Zone Thermostat & Q667 Switching Subbase Q667 Switching Subbase Discharge Air Sensor Honeywell 6RT1Refer to Wiring Notes on Page p RT1 Discharge Air Sensor Assembly Compressor Damage EVP Chiller ApplicationsSystem Evacuation Procedures System Pre-Start ProceduresSystem Pre-Start Procedures Standing Vacuum Test Typical Vacuum Pump HookupEvacuation Time vs. Pressure Rise System Pre-Start Procedures W7100A Discharge Air Controller Economizer Actuator Checkout Zone or Discharge Air Temp ControllerOhms 4200 4000 3800 System Pre-Start Procedures W7100G Chilled Water Controller Master Energy Control Checkout Hazardous Voltage Zone Thermostat Checkout Honeywell T7067 Zone Thermostat 6U37 Voltage Output ramps TerminalsOhms Voltage Imbalance Electrical PhasingVAV W7100A Discharge Air Controller 7U11 Sequence of OperationEconomizer Cycle System Start-Up Chilled Water Temperature Controller 6U11Thermostatic Expansion Valve Condenser Fans W7100G Staging SequenceCompressor Crankcase Heaters Low Ambient DampersPump Down System Start-Up Low Ambient Thermostats Low Ambient Damper Adjustment Factory or Field InstalledLive Electrical Components Hot Gas Bypass OperationEVP Chiller Applications Freezestat Setting200 300 System Airflow Measurement Air Over Evaporator ApplicationRotating Components Verifying Proper Supply Fan RotationCompressor Start-Up All Systems Compressor Damage Live Electrical Components Measuring Subcooling SubcoolingMeasuring Superheat Compressor Oil Pressure Control Switch SettingsMinimum starting Ambient Temperature Recommended Refrigerant CapacitiesCompressor Sequence Typical Compressor Locations Ton Pressure Curve System Start-Up System Start-Up Ton Pressure Curve per Circuit 100 101 Final System Setup Recommended Operating SetpointsSample Maintenance Log At Shutdown Scroll Compressor ReplacementCompressor Operational Sounds At Low Ambient Start-UpService & Maintenance Compressor Circuit Breaker DataFuse Replacement Data Fuse Replacement DataMonthly Maintenance Air Handling EquipmentCoil Cleaning Condensing UnitHazardous Pressures System operationWarranty and Liability Clause Symbols NumericsIndex 111SS-SVX09A-EN

RAUC-C20, RAUC-C40, RAUC-C25, RAUC-C30, RAUC-C60 specifications

Trane, a leader in HVAC solutions, offers innovative air conditioning units designed for superior performance and energy efficiency. Among their advanced products are the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50, which cater to various cooling and heating needs in residential and commercial applications.

The RAUC-C series showcases cutting-edge technology, ensuring effective climate control while minimizing energy consumption. These units are equipped with variable-speed compressors, allowing for precise cooling capacities and reduced noise levels during operation. This feature ensures that users can enjoy optimal comfort without the disruptive noise often associated with traditional HVAC systems.

One of the standout technologies used in the RAUC-C series is Trane’s advanced inverter technology. This system intelligently adjusts the compressor speed based on real-time cooling demands, enhancing efficiency and prolonging the unit's lifespan. Additionally, the units come with high SEER (Seasonal Energy Efficiency Ratio) ratings, making them an excellent choice for those looking to lower their energy bills while maintaining a comfortable indoor environment.

The RAUC-C series units are designed with durability in mind. Constructed with robust materials, these air conditioning systems are built to withstand varying weather conditions. Their compact and lightweight design makes installation straightforward, and they can fit seamlessly into a variety of spaces, from residential homes to commercial buildings.

Another key characteristic of the RAUC-C series is their eco-friendly refrigerant, which meets strict environmental regulations. This not only supports sustainability efforts but also ensures efficient cooling performance. Furthermore, their smart technology capabilities enable integration with modern smart home systems, allowing users to manage their cooling settings remotely for added convenience.

Trane's focus on user-friendly interfaces makes these units easy to operate. The intuitive control systems allow users to customize their cooling preferences easily, providing flexibility to adapt to individual comfort needs.

Overall, the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50 stand out for their energy efficiency, advanced technology, durability, and user-focused design. These features make them reliable choices for anyone seeking efficient and effective heating and cooling solutions.