Trane RAUC-C25, RAUC-C50, RAUC-C30, RAUC-C60 Liquid Line Piping, Liquid Line Interconnecting Tubing

Page 35

Installation

Liquid Line Piping

Liquid line sizes are based on their ability to provide a minimum of 5 degrees F (2.7ºC) of sub- cooling at the expansion valve throughout the unit’s operating system. Increasing the liquid line size does not increase the available sub-cooling. The uniform liquid line size, pre-selected in the Table below, are independent of the line length or rise within the permissible guidelines to maintain this minimum required 5 degree F (2.7ºC) sub-cooling at the expansion valve for a properly charged RAUC unit operating in a normal air conditioning application.

The liquid line should have a slight slope in the direction of flow so that it can be routed with the suction line.

The unit has a liquid line check valve that prevents liquid refrigerant from flowing backward through the liquid line, filling the condenser, and overflowing to the compressor during the “Off” cycle. A relief valve is also installed to prevent the build up of high pressure in the liquid line when the unit is off. For proper operation of the relief valve, the liquid line service valve should not be in the back seated position but cracked open so the relief valve (and the fan pressure switch) is open to the condenser. The line that connects the outlet of the 235 psig relief valve to the liquid line service valve must not be removed.

For more information, refer to the latest edition of Application Guide SS-APG001-EN.

1.Avoid putting liquid lines underground.

2.Route liquid lines as short and direct as possible.

3.Slope liquid lines away form the condensing unit 1-inch for every 10 feet.

4.Only insulate liquid lines that pass through heated areas.

5.Wire solenoid valves according to the field connection diagram for proper pump down operation.

6.The liquid line filter drier should be as close to the solenoid valve as possible.

Note: If the liquid line riser exceeds 10 feet, refer to Tube Size and Component Selection, publication number SS-APG001-EN

Liquid Line Interconnecting Tubing

 

 

OD Vertical

Capacity

OD Horizontal (Per Circuit)

(Per Circuit)

 

 

 

20 Ton

5/8”

5/8”

 

 

 

25 Ton

7/8”

7/8”

 

 

 

30 Ton

7/8”

7/8”

 

 

 

40 Ton

5/8”

5/8”

 

 

 

50 Ton

7/8”

7/8”

 

 

 

60 Ton

7/8”

7/8”

Note: If risers exceed 10 feet, refer to Tube Size and Component Selection, publication number SS-APG001-EN

SS-SVX09A-EN

35

Image 35
Contents June Remote Split System UnitsOverview of Manual Grounding RequiredEnvironmental Concerns Responsible Refrigerant PracticesTable of Contents SS-SVX09A-EN Compressor Nameplate Model Number DescriptionUnit Nameplate Unit Description EVP Chiller Considerations Unit InspectionNo Step Surface Unit ClearancesFoundation Unit Dimensions & Weight InformationInstallation Installation RAUC-C20 Unit Dimensional Data & Recommended Clearances RAUC-C25 Unit Dimensional Data & Recommended Clearances RAUC-C30 Unit Dimensional Data & Recommended Clearances RAUC-C40 Unit Dimensional Data & Recommended Clearances RAUC-C50 Unit Dimensional Data & Recommended Clearances RAUC-C60 Unit Dimensional Data & Recommended Clearances Bphe 20 Evaporator Chiller Dimensions Bphe 25 Evaporator Chiller Dimensions Bphe 30 Evaporator Chiller Dimensions Bphe 40 Evaporator Chiller Dimensions Bphe 50 Evaporator Chiller Dimensions Bphe 60 Evaporator Chiller Dimensions Typical EVP Chiller Weights & General Data Typical Unit Weights & Point Loading DataRigging and Center-of-Gravity Data Rigging Heavy ObjectsTypical Neoprene Isolator Selection & Location Unit IsolationNeoprene Isolators Leveling the Unit Installation Spring IsolatorsTypical Spring Isolator Selection & Location Shipping FastenersCompressor Shipping Hardware Two Manifolded CompressorsRefrigerant Piping Requirements General Unit RequirementsEVP Chilled Water Piping Requirements Main Electrical Power Requirements Hazardous VoltageHazard of Explosion No Controls Units Ground WireField Installed Control Wiring Requirements Volt Control Wiring All UnitsEVP Chiller Piping Refrigerant Line Components Low Voltage Wiring AC & DC Hazardous VoltageVariable Air Volume VAV Units Constant Volume UnitsThermostatic Expansion Valve TEV Liquid Line Moisture Indicator Sight GlassAccess Valves Ports Liquid Line Solenoid ValvesTypical Placement of Split System piping Components Solenoid Valve & Sight Glass w/Moisture IndicatorUse Type L refrigerant grade copper tubing only Suction Line Interconnecting TubingRefrigerant Piping Suction Line PipingLiquid Line Piping Liquid Line Interconnecting TubingTypical Coil Piping For Dual Circuit Units Evaporator PipingFinal Refrigerant Pipe Connections Hot Gas Bypass for Commercial Comfort-Cooling ApplicationsOptional Pressure Gauges Brazing Procedures Hazard of Explosion and Deadly Gases Leak Testing Procedure Hazard of Explosion Chilled Water Piping Evaporator Water-Pressure Drop Water Pressure Gauges Installation Air VentsChiller Flow Switch Water Temperature SensorTypical Piping Recommendations FreezestatFinal Water Piping Connections Optional Flow Switch IllustrationDisconnect Switch External Handle Factory Mounted Option Field Installed Power WiringMain Unit Power Wiring Hazardous Voltage Calculation #1 MCA, MOP, and RDE Power Wire Sizing and Protection DeviceCustomer Connection Wire Range EquationsElectrical Service Sizing Data Installation Calculation #2 Disconnect Switch Sizing DSSControls Using 115 VAC Hazardous Voltage Field Installed Control Wiring Hazardous VoltageHot Gas Bypass All control options EVP Interlocks EVP Flow control 6S58EVP Circulating Pump Interlock Outside Air Thermostat 5S57AC Conductors Controls using 24 VAC Hazardous VoltageControls using DC Analog Input/Outputs Hazardous Voltage DC Conductors Economizer Actuator CircuitEconomizer Actuator Circuit Legend Temperature Control ParametersNo System Control Refer to Wiring Notes on p Installation Discharge Air Sensor Honeywell 6RT3 Variable Air Volume Control Honeywell W7100ANight Setback Hazardous Voltage Suction Line ThermostatEVP Chiller Control W7100G Discharge Chilled Water Controller EVP Chiller Remote Panel Chilled Water Temperature Sensor Honeywell 6RT2Outside Air Thermostat 5S57 Field Provided Refer to Wiring Notes on Page p Thermostat Checkout Constant Volume Control HoneywellThermostat Wiring Electronic Zone Thermostat Honeywell T7067T7067 Electronic Zone Thermostat & Q667 Switching Subbase Discharge Air Sensor Honeywell 6RT1 Q667 Switching SubbaseRefer to Wiring Notes on Page p RT1 Discharge Air Sensor Assembly EVP Chiller Applications Compressor DamageSystem Pre-Start Procedures System Evacuation ProceduresTypical Vacuum Pump Hookup System Pre-Start Procedures Standing Vacuum TestEvacuation Time vs. Pressure Rise System Pre-Start Procedures W7100A Discharge Air Controller Zone or Discharge Air Temp Controller Economizer Actuator CheckoutOhms 4200 4000 3800 System Pre-Start Procedures W7100G Chilled Water Controller Master Energy Control Checkout Hazardous Voltage Zone Thermostat Checkout Honeywell T7067 Terminals Zone Thermostat 6U37 Voltage Output rampsOhms Electrical Phasing Voltage ImbalanceEconomizer Cycle Sequence of OperationVAV W7100A Discharge Air Controller 7U11 Thermostatic Expansion Valve Chilled Water Temperature Controller 6U11System Start-Up W7100G Staging Sequence Condenser FansPump Down Low Ambient DampersCompressor Crankcase Heaters Hot Gas Bypass Operation Low Ambient Damper Adjustment Factory or Field InstalledLive Electrical Components System Start-Up Low Ambient Thermostats200 300 Freezestat SettingEVP Chiller Applications Verifying Proper Supply Fan Rotation Air Over Evaporator ApplicationRotating Components System Airflow MeasurementCompressor Start-Up All Systems Compressor Damage Live Electrical Components Measuring Superheat SubcoolingMeasuring Subcooling Recommended Refrigerant Capacities Pressure Control Switch SettingsMinimum starting Ambient Temperature Compressor OilCompressor Sequence Typical Compressor Locations Ton Pressure Curve System Start-Up System Start-Up Ton Pressure Curve per Circuit 100 101 Recommended Operating Setpoints Final System SetupSample Maintenance Log At Low Ambient Start-Up Scroll Compressor ReplacementCompressor Operational Sounds At ShutdownCompressor Circuit Breaker Data Service & MaintenanceAir Handling Equipment Fuse Replacement DataMonthly Maintenance Fuse Replacement DataCondensing Unit Coil CleaningSystem operation Hazardous PressuresWarranty and Liability Clause Numerics Symbols111 IndexSS-SVX09A-EN

RAUC-C20, RAUC-C40, RAUC-C25, RAUC-C30, RAUC-C60 specifications

Trane, a leader in HVAC solutions, offers innovative air conditioning units designed for superior performance and energy efficiency. Among their advanced products are the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50, which cater to various cooling and heating needs in residential and commercial applications.

The RAUC-C series showcases cutting-edge technology, ensuring effective climate control while minimizing energy consumption. These units are equipped with variable-speed compressors, allowing for precise cooling capacities and reduced noise levels during operation. This feature ensures that users can enjoy optimal comfort without the disruptive noise often associated with traditional HVAC systems.

One of the standout technologies used in the RAUC-C series is Trane’s advanced inverter technology. This system intelligently adjusts the compressor speed based on real-time cooling demands, enhancing efficiency and prolonging the unit's lifespan. Additionally, the units come with high SEER (Seasonal Energy Efficiency Ratio) ratings, making them an excellent choice for those looking to lower their energy bills while maintaining a comfortable indoor environment.

The RAUC-C series units are designed with durability in mind. Constructed with robust materials, these air conditioning systems are built to withstand varying weather conditions. Their compact and lightweight design makes installation straightforward, and they can fit seamlessly into a variety of spaces, from residential homes to commercial buildings.

Another key characteristic of the RAUC-C series is their eco-friendly refrigerant, which meets strict environmental regulations. This not only supports sustainability efforts but also ensures efficient cooling performance. Furthermore, their smart technology capabilities enable integration with modern smart home systems, allowing users to manage their cooling settings remotely for added convenience.

Trane's focus on user-friendly interfaces makes these units easy to operate. The intuitive control systems allow users to customize their cooling preferences easily, providing flexibility to adapt to individual comfort needs.

Overall, the Trane RAUC-C30, RAUC-C20, RAUC-C40, RAUC-C60, and RAUC-C50 stand out for their energy efficiency, advanced technology, durability, and user-focused design. These features make them reliable choices for anyone seeking efficient and effective heating and cooling solutions.