|
| Mounting and Wiring the Control | |
|
|
|
|
| Smoke Detector Notes | • Fire Verification (zone type 16): The control panel will “verify” a fire alarm by | |
|
| resetting the smoke detectors after the first alarm trigger, and then waiting 90 seconds | |
|
| for a second alarm trigger. If the smoke detector or thermostat does not trigger again, | |
|
| the control will disregard the first trigger, and no alarm signal will occur. This feature | |
|
| eliminates false alarms due to electrical or physical transients. | |
|
| SIA Installations: If using fire verification on zones other than zone 1, UL Fire Alarm | |
|
| Listed relay accessories must be used to reset power as described in the Power Reset | |
|
| paragraph above. |
•The zone 1 alarm current supports only one smoke detector in the alarmed state.
•Clean Me Option: If enabled (field *174 = 1; *56 zone programming, response time prompt = 3), certain ESL smoke detectors send “clean me” reports as appropriate. If used, the maximum number of detectors is reduced to 10 (not standard 16). Refer to the ESL documentation included with the smoke detector for information regarding compatibility with the
•Do not use
+ | 5 |
|
|
|
|
|
|
| RELAY |
|
|
|
|
AUX PWR | PROGRAM | BLK |
| + | RED | |
RELAY |
|
|
|
|
| |
OUTPUT | AS ZONE |
|
|
|
| EOL |
TERMINALS | TYPE 54 |
|
|
|
| |
|
|
|
| POWER | ||
| (FIRE ZONE |
|
|
| N.O. | SUPERVISION |
| RESET) |
|
|
| ||
|
|
|
|
| RELAY MODULE | |
| 4 |
|
|
|
| |
| N.C. |
|
|
| ||
|
|
|
|
| ||
CONTACT OPENS |
|
|
|
| USE N.O. | |
|
|
|
| CONTACT, | ||
MOMENTARILY UPON | + |
|
|
| ||
| VIOLET | WHICH CLOSES | ||||
FIRE ALARM RESET |
| |||||
|
| |||||
|
|
|
|
| WHEN POWER | |
|
|
|
|
| IS APPLIED. | |
|
| OR COMBUSTION |
|
|
| |
|
| DETECTOR | 2000 |
|
|
|
|
|
|
|
|
| |
|
| OHMS |
|
|
| |
|
| EOLR |
|
|
| |
TO ZONE TERM. (+) |
|
|
|
| ||
|
|
|
| |||
|
| HEAT |
|
|
| |
|
|
|
|
| wiresmk | |
| DETECTOR |
|
|
| ||
TO ZONE TERM. ( ) |
|
|
|
| ||
|
|
|
|
|
| 4 |
Figure 9a. | ||||||
AUX PWR (+) 5 | _ | BLK | _ | + | RED | |
TO OUTPUT 17 ( ) |
| |||||
PROGRAM OUTPUT 17 |
|
|
|
| EOL | |
FOR "OUT NORM |
|
|
|
| POWER | |
LOW" = YES IN | 79 MENU | + |
|
| N.O. | SUPERVISION |
MODE AND AS ZONE |
|
| RELAY MODULE | |||
|
|
| VIOLET | |||
TYPE 54 IN |
|
| ||||
80 MENU MODE | OR COMBUSTION |
|
|
| USE N.O. | |
|
| DETECTOR | 2000 |
|
| CONTACT, |
|
|
|
|
| ||
|
|
| OHMS |
|
| WHICH CLOSES |
|
|
| EOLR |
|
| WHEN POWER |
|
|
|
|
|
| IS APPLIED. |
TO ZONE TERM. (+) |
|
|
|
| 4 | |
|
| HEAT |
|
|
| |
TO ZONE TERM. ( ) | DETECTOR |
|
|
| ||
|
|
|
| |||
|
|
|
|
|
|
Figure 9b. 4-Wire Smoke Detector Using Output 17 for Power Reset
4219/4229 Expansion | 1. Connect each module to the control’s keypad terminals and set the device addresses. |
Zones | • |
•
2.Connect sensors to the module’s loops. See Figure 8 on the following page.
• Use 1000 ohm
• Expansion zones have normal response time
3.If using relays with the 4229, connect the desired field wiring to the unit's relay contact terminals.