Honeywell K5305-1V5 setup guide Sounder Bell Connections, Basic Connections, Supervised output

Page 10

Installation and Setup Guide

Sounder (Bell) Connections

Basic Connections

3 4

ALARM OUTPUT

 

10.5 - 13.5 VDC

 

2A MAX.

V0

 

spkr conn-001-

Make sounder connections to alarm output terminals 3 (+) and 4 (–).

The 12VDC sounder output activates when an alarm occurs.

Total current drawn from this output cannot exceed 2 amps (going beyond 2 amps will overload the power supply, or may cause the electronic circuit protecting the sounder output to trip).

You must install a battery, since the battery supplies this current.

Supervised output

1.Cut the red Bell Supervision Jumper located above terminals 2 and 3 on the PC board.

2.Connect a 2k ohm resistor across the terminals of the last sounder. See Figure 5.

This control complies with NFPA requirements for temporal pulse sounding of fire notification appliances. Temporal pulse sounding for a fire alarm consists of: 3 pulses – pause – 3 pulses – pause – 3 pulses–etc..

UL

Use only UL Listed sounding devices for UL installations.

Bell supervision is required for fire alarm installations.

The total current drawn from the alarm output and the auxiliary power output, combined, cannot exceed 600 mA. In addition, the sounding device must be a UL Listed audible signal appliance rated to operate in a 10.2-13.8 VDC voltage range, and must be mounted indoors.

TERMINALS ON

EXTERNAL ALARM

 

 

CONTROL BOARD

SOUNDER

 

 

4

 

 

 

ALARM

 

2000

 

OBSERVE

OHM

 

OUTPUT

 

POLARITY

EOL

 

TERMINALS

 

+

RESISTOR

+

 

 

 

 

3

 

 

 

2

IF BELL SUPERVISION IS ENABLED

 

 

 

 

 

 

(RED JUMPER ON CONTROL BOARD IS CUT)

 

 

CONNECT A 2000 OHM RESISTOR ACROSS

-V0

 

THE EXTERNAL SOUNDER AS SHOWN BY

CUT RED JUMPER ON CONTROL

THE DOTTED LINE.

 

001-

 

 

sounder

BOARD TO ENABLE BELL

DO NOT CONNECT THE RESISTOR AT THE

(SOUNDER) SUPERVISION.

ALARM OUTPUT TERMINALS THEMSELVES!

Figure 5. Sounder Wiring (Supervised)

Connecting the Keypads and Other Addressable Devices

Connections

 

 

4 _

 

 

 

5 +

 

 

 

6 IN

 

 

 

7 OUT

BLACK

RED

GREEN

YELLOW

AR

 

 

 

MED

 

 

 

READY

 

 

 

 

 

 

conn-001-V0

Connect keypads and other addressable devices (4204, 4219, 4229, 4286, 5881, LRR, etc.) to the control’s keypad terminals as shown on the Summary of Connections diagram. The system supports up to 8 keypads, which can be assigned to partitions in any combination (see program fields *190-*196).

Determine wire size using the Wire Run Chart on the following page. For single 4-wire runs, determine the current drawn by all units, then refer to the Wiring Run chart to determine the maximum length that can be safely used for each wire size.

Supplementary Power (optional)

UL Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these keypads in case of AC power loss.

The battery-backed power supply should have enough power to supply the keypads with the UL required minimum standby power time.

Use supplementary power if the control’s aux. power load for all devices exceeds 600mA (suggested power supply: AD12612). Connect as shown in Figure 6. Be sure to connect the negative (–) terminal on the power supply unit to terminal 4 (AUX –) on the control.

IMPORTANT: Keypads powered from supplies that do not have a backup battery will not function if AC power is lost. Make sure to power at least one keypad in each partition from the control’s auxiliary power output.

SUPPLEMENTARY

 

CONTROL TERMINAL STRIP

POWER SUPPLY

 

 

 

 

 

 

 

 

 

+

 

AUX. AUX. DATA DATA

 

 

 

 

+

 

IN

OUT

 

 

 

4

5

6

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REDWIRE

WIREBLK

GRNWIRE

WIREYEL

DIRECTLY TO

WIREBLK

REDWIRE

GRNWIRE

WIREYEL

 

 

 

 

 

IMPORTANT:

 

 

 

 

 

 

 

 

 

MAKE THESE

 

 

 

 

 

KEYPADTO

KEYPADTO

KEYPADTO

KEYPADTO

CONNECTIONS

KEYPADTO

KEYPADTO

KEYPADTO

KEYPADTO

V0-supplypwrsupp

SCREW

 

 

 

 

 

 

 

 

 

 

 

 

 

TERMINALS AS

 

 

 

 

 

 

 

 

 

SHOWN.

 

 

 

 

 

Figure 6. Using a Supplementary Power Supply

2-4

Image 10
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Features and Installation Highlights Capabilities and FunctionsCompatible Devices Important Installation Highlights Installer Please ReadDevice Mounting and Wiring the Control Installing the Control Cabinet and PC BoardAuxiliary Device Current Draw Worksheet AC Power, Battery, and Ground Connections Wire Run ChartBasic Connections Connecting the Keypads and Other Addressable DevicesSounder Bell Connections Supervised outputLong Range Radio Connections Table of Device AddressesKeypad Notes Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Smoke Detector Notes ZonesRF Receiver No. of Zones Installing the RF Receiver and Wireless Transmitter ZonesCompatible Receivers Receiver ConnectionsTransmitter Battery Life Installing a 5800TMInstalling ModuleInstalling a Keyswitch Keyswitch ConnectionsPowerline Carrier Devices 4204/4229 Relay ModulesOn-Board Triggers With the control as shown belowPhone Module Problems Phone Line 4285/4286 Phone ModuleAudio Alarm Verification Connections AAV, listen-In BankAbout Programming Programming OverviewMechanics of Programming Zone Type Definitions Alarm Alarm by NightHr Silent Alarm Auxiliary AlarmConfigurable No AlarmKeyswitch Response TypeAbout Data Field Programming System Setup Fields ∗20 ∗29Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Priority Burglary Dialer DelayDynamic Signaling Delay Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Event Log Enables Misc. Fault Delay TimeProgram Mode Lockout Options Phone Line Monitor EnablePager Programming Fields Pager 1 Characters 172Pager Delay Option for AlarmsClean Me Option Pager 1 Report OptionsConfigurable Zone Type Options Configurable Zone Type FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesTouch Screen Keypad AUI Enable Keypad Programming FieldsInstallation and Setup Guide Zones and Partitions Menu Mode ProgrammingZone Programming Procedure About Zone Programming ∗56 and ∗58 Menu ModesSummary Screen Hardwire TypeZone Number Zone Type ZTLoop Number Change Input Device typeSerial number Entry and Loop Number Entry Enroll Summary∗58 Expert Programming Mode Procedures Completing Zone ProgrammingTo Delete a Serial Number Zone ProgrammingSerial number ConfirmTemplate Display Wireless Key Programming TemplatesTemplate Number Partition5804BD 2-Way Wireless Key Transmitter Wireless Key Predefined Default TemplatesWireless Key Transmitter Not ConfirmedProgramming Output Devices About Output Device Programming *79/*80 Menu ModeMenu Mode Output Device Mapping Output IdentificationRelay Position Output TypeModule Addresses Output Function No Menu Mode Defining Output FunctionsActivated By = off = Change Device State = Close for 2 seconds Output Action01-08 = zone list ∗ to continue = Stay ClosedAbout Zone Lists *81 Menu Mode Zone List ProgrammingFunction Key About Function Keys *57 Menu ModeProgramming Function Keys Partition NumbeAbout Descriptor Programming *82 Menu Mode Programming Zone Descriptors Menu Mode ∗82Accept Second Word Accept First WordSecond 3-Digit Index No Assigning Partition/Custom Message DescriptorsCharacter Ascii Chart For Adding Custom Words For Entering Zone DescriptorsSchedule Number Programming Installer and User SchedulesStart Time = repeat every third week 4 = repeat every fourth week Repeat OptionRandomize For events 01 Report Code Formats System Communication and OperationPanel Communication with Central Station DigitWhere Code for Type +1/4+1 Report Standard ExpandedSome event codes may not apply to certain control panels Ademco Contact IDCode Definition Attributes Values Keyfob must be enrolled in system first see Wireless KeySystem Security Codes Level User No FunctionsVoice Keypads Keypad CommandsKeypad Functions Function DescriptionSetting the Real-Time Clock Keys Displayed as Zone ∗ /1 ∗ /#Various System Trouble Displays Alpha Display Fixed Disp MeaningInstallation and Setup Guide Checking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportElectrical Specifications & AccessoriesSecurity Control CommunicationWire Smoke Detector Detector TypeCompatible 5800 Series Transmitters Table Series Transmitter Input Loop IdentificationModel Product Input Type Description Can be used to turn the burglary protection on and off 5827 Wireless KeypadTo be transmitted Regulatory Agency Statements Industrie CanadaUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations and Warranty Limitations of this Alarm System10-8 Index 10-10 Summary of Connections Limited Warranty K5305-1V5 10/04 Rev. a