Honeywell K5305-1V5 setup guide Audio Alarm Verification Connections AAV, listen-In, Bank

Page 20

Installation and Setup Guide

Audio Alarm Verification Connections

(AAV, “listen-In”)

Refer to the connection diagrams below. One diagram shows connections when a 4285/4286 Phone Module is used, the other shows connections when the 4285/4286 is not used.

Connections use one of the on-board triggers.

Set field *91 for AAV and program the appropriate output (output 17 or 18) using *80 Menu mode: select zone type 60 and output action 1 (close for 2 seconds) or action 2 (stay closed).

For voice session monitoring, connect an EOLR zone to UVCM module terminals 6 & 7, and program the zone as zone type 81 (*56 Menu mode).

E.g., Using output 18 for the trigger, program an output function in *80 Menu mode as: ZT = 60, P = 0, Action = 1, Device = 18

Suggested AAV Module: ADEMCO UVS (shown) or Eagle 1250

UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS system).

 

 

 

 

 

 

 

 

5

TRIGGER

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

ZONE

 

 

 

 

EARTH

 

 

 

 

 

 

CONTROL

OUTPUT

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

 

 

 

 

AUXILIARY

4

5

 

21

22

23

24

25

 

 

 

 

AUDIO LEVEL

 

 

 

 

 

 

 

 

 

 

 

 

ADJUSTMENT

GND

+12VDC

 

 

 

 

 

 

 

 

 

 

 

TRIM POT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EOL

 

 

 

 

 

 

 

UVCM

 

 

 

34

 

 

RING

 

 

 

 

 

 

 

MODULE

 

 

 

TIP

 

 

 

 

 

 

 

 

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED (R)

 

 

 

 

 

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

 

 

 

 

 

GREEN (T)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RJ31X

 

 

 

 

 

 

30

 

 

 

 

 

 

GREY (R)

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

29

 

 

 

 

 

 

BROWN (T)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REFER TO UVCM MODULE

 

 

 

 

 

 

 

 

 

 

 

 

 

INSTRUCTIONS FOR

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTIONS TO AUDIO

 

 

 

 

11

 

 

OPTIONAL

 

 

 

 

 

SPEAKERS AND MICROPHONE.

 

 

 

 

 

 

 

 

 

 

 

 

765 8

BANK2

 

 

 

 

MONITORING ZONE

 

 

 

 

 

 

 

 

910

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(USE ZONE TYPE 81)

 

 

 

 

2 = OFF

2 = ON

ON

4321

SWITCH

 

876

 

 

 

 

 

 

TO

INCOMING

SWITCH

SWITCH

 

 

 

 

 

 

 

 

 

 

 

PREMISES

 

BANK 1

BANK 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HANDSET

 

1 = OFF

1 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 = OFF

3 = OFF

 

 

 

FALLING VOICE TRIG

5

 

 

 

 

 

 

 

PHONE LINE

4 = OFF

4 = ON

 

8

1

 

 

 

 

 

 

 

 

5 = OFF

5 = ON

ON

6543217

BANKSWITCH

 

4321

 

 

 

 

 

 

 

003V0-

6 = OFF

6 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

7 = OFF

7 = ON

 

 

 

 

 

 

 

 

 

 

 

 

 

8 = ON

8 = ON

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+12VDC IN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aav uvcm-

Figure 17a. Connection of AAV Unit When Not Using a 4285/4286 Phone Module

NOTE:

REFER TO UVCM MODULE INSTRUCTIONS FOR CONNECTIONS TO AUDIO SPEAKERS AND MICROPHONE.

SWITCH

SWITCH

BANK 1

BANK 2

1

= OFF

1

= ON

2

= OFF

2

= ON

3

= OFF

3

= OFF

4

= OFF

4

= ON

5

= OFF

5

= ON

6

= OFF

6

= ON

7

= OFF

7

= ON

8

= ON

8

= ON

 

 

 

 

 

5

TRIGGER

 

 

 

 

 

 

 

 

 

CONNECTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

 

ZONE

 

 

 

 

 

 

CONTROL

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

TERMINALS

 

 

 

 

AUXILIARY

 

4

5

 

 

21

22

23

24

25

AUDIO LEVEL

 

 

 

 

 

 

 

 

 

 

ADJUSTMENT

 

GND

+12VDC

 

 

 

 

 

 

 

TRIM POT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EOL

 

 

 

 

UVCM

RING

34

 

 

 

RING

 

 

 

 

 

 

 

 

 

 

 

 

MODULE

 

 

 

TIP

 

 

 

 

TIP

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED (R)

 

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

 

GREEN (T)

30

 

GREY (R)

29

OPTIONAL

BROWN (T)

MONITORING

 

 

 

ZONE

 

 

CONNECTION

 

11

(USE ZONE

 

TYPE 81)

 

EARTH

GROUND

RJ31X

 

8

 

7

 

6

 

5

 

4

 

3

ON

1 2

 

8

 

7

 

6

 

5

 

4

 

3

ON

1 2

SWITCH BANK 1 SWITCH BANK 2

 

10

 

9

 

8

 

7

 

6

FALLING VOICE TRIG

5

 

4

 

3

GND

2

 

+12VDC IN

1

4285/4286

4

3

2

1

TO

PREMISES

HANDSET

INCOMING

PHONE LINE

aav_uvcm-004-V0

Figure 17b. Connection of AAV Unit When Using a 4285 or 4286 Phone Module

2-14

Image 20
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Features and Installation Highlights Capabilities and FunctionsDevice Important Installation Highlights Installer Please ReadCompatible Devices Mounting and Wiring the Control Installing the Control Cabinet and PC BoardAuxiliary Device Current Draw Worksheet AC Power, Battery, and Ground Connections Wire Run ChartConnecting the Keypads and Other Addressable Devices Sounder Bell ConnectionsBasic Connections Supervised outputTable of Device Addresses Keypad NotesLong Range Radio Connections Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Smoke Detector Notes ZonesInstalling the RF Receiver and Wireless Transmitter Zones Compatible ReceiversRF Receiver No. of Zones Receiver ConnectionsInstalling a 5800TM InstallingTransmitter Battery Life ModuleInstalling a Keyswitch Keyswitch ConnectionsPowerline Carrier Devices 4204/4229 Relay ModulesOn-Board Triggers With the control as shown belowPhone Module Problems Phone Line 4285/4286 Phone ModuleAudio Alarm Verification Connections AAV, listen-In BankMechanics of Programming Programming OverviewAbout Programming Zone Type Definitions Alarm by Night Hr Silent AlarmAlarm Auxiliary AlarmNo Alarm KeyswitchConfigurable Response TypeSystem Setup Fields ∗20 ∗29 Data Field ProgrammingAbout Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Burglary Dialer Delay Dynamic Signaling DelayDynamic Signaling Priority Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Misc. Fault Delay Time Program Mode Lockout OptionsEvent Log Enables Phone Line Monitor EnablePager Programming Fields 172Pager Delay Option for Alarms Clean Me OptionPager 1 Characters Pager 1 Report OptionsConfigurable Zone Type Fields Configurable Zone TypeConfigurable Zone Type Options Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesTouch Screen Keypad AUI Enable Keypad Programming FieldsInstallation and Setup Guide Menu Mode Programming Zone Programming ProcedureZones and Partitions About Zone Programming ∗56 and ∗58 Menu ModesHardwire Type Zone NumberSummary Screen Zone Type ZTInput Device type Serial number Entry and Loop Number EntryLoop Number Change Enroll Summary∗58 Expert Programming Mode Procedures Completing Zone ProgrammingZone Programming Serial numberTo Delete a Serial Number ConfirmWireless Key Programming Templates Template NumberTemplate Display PartitionWireless Key Predefined Default Templates Wireless Key Transmitter5804BD 2-Way Wireless Key Transmitter Not ConfirmedAbout Output Device Programming *79/*80 Menu Mode Menu Mode Output Device MappingProgramming Output Devices Output IdentificationModule Addresses Output TypeRelay Position Activated By Menu Mode Defining Output FunctionsOutput Function No Output Action 01-08 = zone list ∗ to continue= off = Change Device State = Close for 2 seconds = Stay ClosedAbout Zone Lists *81 Menu Mode Zone List ProgrammingAbout Function Keys *57 Menu Mode Programming Function KeysFunction Key Partition NumbeAbout Descriptor Programming *82 Menu Mode Programming Zone Descriptors Menu Mode ∗82Accept First Word Second 3-Digit Index NoAccept Second Word Assigning Partition/Custom Message DescriptorsCharacter Ascii Chart For Adding Custom Words For Entering Zone DescriptorsStart Time Programming Installer and User SchedulesSchedule Number Randomize For events 01 Repeat Option= repeat every third week 4 = repeat every fourth week System Communication and Operation Panel Communication with Central StationReport Code Formats DigitWhere Code for Type +1/4+1 Report Standard ExpandedCode Definition Ademco Contact IDSome event codes may not apply to certain control panels Keyfob must be enrolled in system first see Wireless Key System Security CodesAttributes Values Level User No FunctionsKeypad Commands Keypad FunctionsVoice Keypads Function DescriptionSetting the Real-Time Clock Keys Displayed as Zone ∗ /1 ∗ /#Various System Trouble Displays Alpha Display Fixed Disp MeaningInstallation and Setup Guide Testing the System About Test ProceduresChecking Transmitter Enrollment Sniffer Mode System TestGo/No Go Test Mode Automatic Standby Battery TestsDialer Communication Test and Periodic Test Reports Automatic Periodic Test ReportSpecifications & Accessories Security ControlElectrical CommunicationWire Smoke Detector Detector TypeModel Product Input Type Description Series Transmitter Input Loop IdentificationCompatible 5800 Series Transmitters Table To be transmitted 5827 Wireless KeypadCan be used to turn the burglary protection on and off Regulatory Agency Statements Industrie CanadaUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations and Warranty Limitations of this Alarm System10-8 Index 10-10 Summary of Connections Limited Warranty K5305-1V5 10/04 Rev. a