Honeywell K5305-1V5 Zone Number, Summary Screen, Zone Type ZT, Partition No. P VISTA-20P

Page 38

Installation and Setup Guide

Enter Zn Num.

 

(00 = Quit)

10

Zone Number

VISTA-20P: wired 01-08 (and 09-48†); wireless 09-48; RF button zones 49-64

VISTA-15P: wired 01-06 (and 07-22†); wireless 09-34; RF button zones 49-56

Both Controls: 91 = addr. device report enable; 92 = duress report enable 95, 96, 99 =emerg. zones

[] to continue; 00 to quit

† if zone expanders are used.

Enter the zone number that you wish to program. Zone 10 has been entered in the example display at left.

Enter a report code for zone 91 to enable addressable device reporting. Enter a report code for zone 92 to enable duress reporting.

95, 96, 99 are emergency (panic) key zones.

 

 

 

 

 

Summary Screen

 

Zn ZT P RC

In: L

 

[] to continue

 

10 00

1 10

RF:

1

 

A summary display appears.

 

 

 

 

 

 

OR

 

 

 

 

 

 

 

“IN: L” appears for wireless zones and indicates input type and loop.

 

Zn ZT P RC

In: AD

“IN: AD” appears for hardwire expansion zones (AW) and indicates the module’s address

 

10 00

1 10

AW: 07

(AD), which is based on the zone number.

 

OR

 

 

 

“HW: RT” appears for hardwire zones and indicates configuration (EOL, NO, NC, zone

 

Zn ZT P RC

HW: RT

doubling, double-balanced) and response time selection.

 

10 00

1 10

EL

1

 

 

 

 

 

 

 

 

 

 

 

 

 

10 Zone Type

Perimeter 03

Zone Type (ZT)

See table below.

Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code from the list below:

Note: If 00 is entered, Delete Zone ? will be displayed.

00

= Not used

07

= 24-Hr Audible

20

= Arm–STAY*

01

= Entry/exit #1

08

= 24-Hr Aux

21

= Arm–AWAY*

02

= Entry/exit #2

09

= Fire

22

= Disarm*

03

= Perimeter

10

= Interior w/Delay

23

= No Alarm Resp

04

= Interior Follower

12 = Monitor Zone

24

= Silent Burglary

05

= Day/Night

14

= Carbon Monoxide

77

= Keyswitch

06

= 24-Hr Silent

16

= Fire w/Verify

81 = AAV Mon. Zone

*5800 button-type transmitters only

 

 

90-91 = Configurable

 

 

 

Partition No. (P) (VISTA-20P)

 

10 Partition

 

 

 

1-3 = partition (3 = common); [] to continue

 

 

1

 

 

Enter the Partition number for this zone. Partition 1 is shown entered.

 

 

 

 

 

 

 

 

 

Report Code (RC)

 

10 Report Code

 

First Digit: 1-9, #+10 for 0, #+11 for B, #+12 for C, #+13 for D, #+14 for E, #+15 for F

 

1st 01 2nd 00 10

 

00 to disable

 

 

Second Digit: same as above; [] to continue

 

 

 

 

Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn

 

 

consisting of 2 numerical digits. For example, for a report code of “10,” enter 01 and 00.

 

 

For Contact ID®, entering any non-zero entry as the first digit enables the report code for

 

 

this zone. Refer to the System Communication section for information about report codes

 

 

and formats.

 

 

Hardwire Type

 

02 HARDWIRE TYPE

 

0 = EOL; 1 = NC; 2 = NO; 3 = zn doubling (ZD) †; 4 = dble-balanced (DB)

EOL

0

[] to continue

VISTA-20P

 

 

 

 

This prompt appears only for zone numbers 02-08.

Zone 1 is automatically set for EOL operation.

02 Response Time

1

Response Time (RT)

0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 seconds; [] to continue

This prompt appears only for hard-wired zones 01-08 (zone 02 is the display shown). Option 3: used for “clean me” option on zone 1 (see field ∗174).

NOTE: If zone doubling is being used, the response time selected for zones 02-08 automatically applies to each zone’s associated doubled zone.

5-2

Image 38
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Features and Installation Highlights Capabilities and FunctionsDevice Important Installation Highlights Installer Please ReadCompatible Devices Mounting and Wiring the Control Installing the Control Cabinet and PC BoardAuxiliary Device Current Draw Worksheet AC Power, Battery, and Ground Connections Wire Run ChartBasic Connections Connecting the Keypads and Other Addressable DevicesSounder Bell Connections Supervised outputLong Range Radio Connections Table of Device AddressesKeypad Notes Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Smoke Detector Notes ZonesRF Receiver No. of Zones Installing the RF Receiver and Wireless Transmitter ZonesCompatible Receivers Receiver ConnectionsTransmitter Battery Life Installing a 5800TMInstalling ModuleInstalling a Keyswitch Keyswitch ConnectionsPowerline Carrier Devices 4204/4229 Relay ModulesOn-Board Triggers With the control as shown belowPhone Module Problems Phone Line 4285/4286 Phone ModuleAudio Alarm Verification Connections AAV, listen-In BankMechanics of Programming Programming OverviewAbout Programming Zone Type Definitions Alarm Alarm by NightHr Silent Alarm Auxiliary AlarmConfigurable No AlarmKeyswitch Response TypeAbout Data Field Programming System Setup Fields ∗20 ∗29Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Priority Burglary Dialer DelayDynamic Signaling Delay Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Event Log Enables Misc. Fault Delay TimeProgram Mode Lockout Options Phone Line Monitor EnablePager Programming Fields Pager 1 Characters 172Pager Delay Option for AlarmsClean Me Option Pager 1 Report OptionsConfigurable Zone Type Options Configurable Zone Type FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesTouch Screen Keypad AUI Enable Keypad Programming FieldsInstallation and Setup Guide Zones and Partitions Menu Mode ProgrammingZone Programming Procedure About Zone Programming ∗56 and ∗58 Menu ModesSummary Screen Hardwire TypeZone Number Zone Type ZTLoop Number Change Input Device typeSerial number Entry and Loop Number Entry Enroll Summary∗58 Expert Programming Mode Procedures Completing Zone ProgrammingTo Delete a Serial Number Zone ProgrammingSerial number ConfirmTemplate Display Wireless Key Programming TemplatesTemplate Number Partition5804BD 2-Way Wireless Key Transmitter Wireless Key Predefined Default TemplatesWireless Key Transmitter Not ConfirmedProgramming Output Devices About Output Device Programming *79/*80 Menu ModeMenu Mode Output Device Mapping Output IdentificationModule Addresses Output TypeRelay Position Activated By Menu Mode Defining Output FunctionsOutput Function No = off = Change Device State = Close for 2 seconds Output Action01-08 = zone list ∗ to continue = Stay ClosedAbout Zone Lists *81 Menu Mode Zone List ProgrammingFunction Key About Function Keys *57 Menu ModeProgramming Function Keys Partition NumbeAbout Descriptor Programming *82 Menu Mode Programming Zone Descriptors Menu Mode ∗82Accept Second Word Accept First WordSecond 3-Digit Index No Assigning Partition/Custom Message DescriptorsCharacter Ascii Chart For Adding Custom Words For Entering Zone DescriptorsStart Time Programming Installer and User SchedulesSchedule Number Randomize For events 01 Repeat Option= repeat every third week 4 = repeat every fourth week Report Code Formats System Communication and OperationPanel Communication with Central Station DigitWhere Code for Type +1/4+1 Report Standard ExpandedCode Definition Ademco Contact IDSome event codes may not apply to certain control panels Attributes Values Keyfob must be enrolled in system first see Wireless KeySystem Security Codes Level User No FunctionsVoice Keypads Keypad CommandsKeypad Functions Function DescriptionSetting the Real-Time Clock Keys Displayed as Zone ∗ /1 ∗ /#Various System Trouble Displays Alpha Display Fixed Disp MeaningInstallation and Setup Guide Checking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportElectrical Specifications & AccessoriesSecurity Control CommunicationWire Smoke Detector Detector TypeModel Product Input Type Description Series Transmitter Input Loop IdentificationCompatible 5800 Series Transmitters Table To be transmitted 5827 Wireless KeypadCan be used to turn the burglary protection on and off Regulatory Agency Statements Industrie CanadaUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations and Warranty Limitations of this Alarm System10-8 Index 10-10 Summary of Connections Limited Warranty K5305-1V5 10/04 Rev. a