Installation and Setup Guide
Enter Zn Num. |
|
(00 = Quit) | 10 |
Zone Number
Both Controls: 91 = addr. device report enable; 92 = duress report enable 95, 96, 99 =emerg. zones
[∗] to continue; 00 to quit | † if zone expanders are used. |
Enter the zone number that you wish to program. Zone 10 has been entered in the example display at left.
Enter a report code for zone 91 to enable addressable device reporting. Enter a report code for zone 92 to enable duress reporting.
95, 96, 99 are emergency (panic) key zones.
|
|
|
|
| Summary Screen |
| Zn ZT P RC | In: L | |||
| [∗] to continue | ||||
| 10 00 | 1 10 | RF: | 1 | |
| A summary display appears. | ||||
|
|
|
|
| |
| OR |
|
|
| |
|
|
|
| “IN: L” appears for wireless zones and indicates input type and loop. | |
| Zn ZT P RC | In: AD | “IN: AD” appears for hardwire expansion zones (AW) and indicates the module’s address | ||
| 10 00 | 1 10 | AW: 07 | (AD), which is based on the zone number. | |
| OR |
|
|
| “HW: RT” appears for hardwire zones and indicates configuration (EOL, NO, NC, zone |
| Zn ZT P RC | HW: RT | doubling, | ||
| 10 00 | 1 10 | EL | 1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
10 Zone Type
Perimeter 03
Zone Type (ZT)
See table below.
Each zone must be assigned to a zone type, which defines the way in which the system responds to faults in that zone. Enter the Zone Type code from the list below:
Note: If 00 is entered, Delete Zone ? will be displayed.
00 | = Not used | 07 | = | 20 | = |
01 | = Entry/exit #1 | 08 | = | 21 | = |
02 | = Entry/exit #2 | 09 | = Fire | 22 | = Disarm* |
03 | = Perimeter | 10 | = Interior w/Delay | 23 | = No Alarm Resp |
04 | = Interior Follower | 12 = Monitor Zone | 24 | = Silent Burglary | |
05 | = Day/Night | 14 | = Carbon Monoxide | 77 | = Keyswitch |
06 | = | 16 | = Fire w/Verify | 81 = AAV Mon. Zone | |
*5800 |
|
|
|
|
| Partition No. (P) |
| 10 Partition |
| |
|
| ||
|
| 1 | |
|
| Enter the Partition number for this zone. Partition 1 is shown entered. | |
|
|
| |
|
|
|
|
|
| Report Code (RC) |
| 10 Report Code | |
| First Digit: | |
| 1st 01 2nd 00 10 | |
| 00 to disable | |
|
| Second Digit: same as above; [∗] to continue |
|
| |
|
| Enter the report code for this zone, which consists of 2 hexadecimal digits, each in turn |
|
| consisting of 2 numerical digits. For example, for a report code of “10,” enter 01 and 00. |
|
| For Contact ID®, entering any |
|
| this zone. Refer to the System Communication section for information about report codes |
|
| and formats. |
|
| Hardwire Type |
| |
02 HARDWIRE TYPE |
| |||
0 = EOL; 1 = NC; 2 = NO; 3 = zn doubling (ZD) †; 4 = | ||||
EOL | 0 | |||
[∗] to continue | † | |||
|
| |||
|
|
This prompt appears only for zone numbers
Zone 1 is automatically set for EOL operation.
02 Response Time
1
Response Time (RT)
0 = 10mSec; 1 = 350mSec; 2 = 700mSec; 3 = 1.2 seconds; [∗] to continue
This prompt appears only for
NOTE: If zone doubling is being used, the response time selected for zones