Honeywell K5305-1V5, VISTA 20P, VISTA-20PSIA, VISTA-15P, VISTA-15PSIA setup guide UL Notices

Page 70

Installation and Setup Guide

UL NOTICES

1.Entry Delay No. 1 and No. 2 (fields 35, 36) cannot be greater than 30 seconds for UL Residential Burglar Alarm installations, and entry delay plus dial delay should not exceed 1 minute. For UL Commercial Burglar Alarm installations, total entry delay may not exceed 45 seconds.

2.For UL Commercial Burglar Alarm (Grade AA) and UL Residential Burglar Alarm installations with line security, total exit delay time must not exceed 60 seconds. For UL Burglar Alarm installations without line security (Grade A), total exit delay time must not exceed 120 seconds.

3.The maximum number of reports per armed period (field 93) must be set to “0” (unlimited) for UL installations.

4.Periodic testing (see scheduling mode) must be at least every 24 hours.

5.Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL installations (Aux power 500mA max.).

6.All partitions must be owned and managed by the same person(s).

7.All partitions must be part of one building at one street address.

8.If used, the audible alarm device(s) must be placed where it/they can be heard by all partitions.

9.For UL commercial burglar alarm installations the control unit must be protected from unauthorized access. The tamper switch installed to protect the control unit enclosure door is suitable for this purpose.

10.Remote downloading without an alarm company technician on-site (unattended downloading) is not permissible for UL installations.

11.Auto-disarming is not a UL Listed feature.

Notes for SIA Installations

1.As SIA limits for delay of alarm reporting and sounding can exceed UL limits for commercial and residential applications, the following UL requirements per UL681 are provided:

The maximum time that a control unit shall be programmed to delay the transmission of a signal to a remote monitoring location, or to delay the energizing of a local alarm sounding device to permit the alarm system user to enter and disarm the system, or to arm the system and exit shall not exceed:

a)60 seconds for a system with standard line security or encrypted line security,

b)120 seconds for a system without standard line security or encrypted line security, or

c)120 seconds for a system that does not transmit an alarm signal to a remote monitoring location.

2.*34 Exit Delay: minimum exit delay is 45 seconds

3.*35/*36 Entry Delay 1 and 2: minimum entry delay is 30 seconds.

4.*39 Power Up in Previous State: must be “1,” power up in previous state

5.*40 PABX Access Code or Call Waiting Disable: If call waiting is used, call waiting disable option in field *91 must be set.

6.*50 Burglary Dial Delay: delay must be minimum of 30 seconds.

7.*59 Exit Error Alarm Report Code: Always enabled.

8.*69 Recent Closing Report Code: Always enabled.

9.*91 Option Selection: Exit Delay option should be enabled. If call waiting is used, Call Waiting Disable must be set to “1” (enabled).

10.*93 No. reports in Armed Period: Must be set for 1 or 2 report pairs.

9-2

Image 70
Contents Ademco Vista Series Recommendations for Proper Protection Table Of Contents Table Of Contents Features and Installation Highlights Capabilities and FunctionsCompatible Devices Important Installation Highlights Installer Please ReadDevice Mounting and Wiring the Control Installing the Control Cabinet and PC BoardAuxiliary Device Current Draw Worksheet AC Power, Battery, and Ground Connections Wire Run ChartBasic Connections Connecting the Keypads and Other Addressable DevicesSounder Bell Connections Supervised outputLong Range Radio Connections Table of Device AddressesKeypad Notes Size MA or less 100 mA 300 mA 500 mA 600 mAHardwire Zones and Zone Expansion Smoke Detector Notes ZonesRF Receiver No. of Zones Installing the RF Receiver and Wireless Transmitter ZonesCompatible Receivers Receiver ConnectionsTransmitter Battery Life Installing a 5800TMInstalling ModuleInstalling a Keyswitch Keyswitch ConnectionsPowerline Carrier Devices 4204/4229 Relay ModulesOn-Board Triggers With the control as shown belowPhone Module Problems Phone Line 4285/4286 Phone ModuleAudio Alarm Verification Connections AAV, listen-In BankAbout Programming Programming OverviewMechanics of Programming Zone Type Definitions Alarm Alarm by NightHr Silent Alarm Auxiliary AlarmConfigurable No AlarmKeyswitch Response TypeAbout Data Field Programming System Setup Fields ∗20 ∗29Data Field Programming Zone Sounds & Timing ∗31-∗39Dialer Programming ∗40 ∗50 Dynamic Signaling Priority Burglary Dialer DelayDynamic Signaling Delay Zone Programming Menu ModeSystem Status Report Codes Miscellaneous System Fields Event Log Enables Misc. Fault Delay TimeProgram Mode Lockout Options Phone Line Monitor EnablePager Programming Fields Pager 1 Characters 172Pager Delay Option for AlarmsClean Me Option Pager 1 Report OptionsConfigurable Zone Type Options Configurable Zone Type FieldsConfigurable Zone Type Zone Type 90 Report CodesConfigurable Zone Type Charts Zone Conditions Represented EntriesTouch Screen Keypad AUI Enable Keypad Programming FieldsInstallation and Setup Guide Zones and Partitions Menu Mode ProgrammingZone Programming Procedure About Zone Programming ∗56 and ∗58 Menu ModesSummary Screen Hardwire TypeZone Number Zone Type ZTLoop Number Change Input Device typeSerial number Entry and Loop Number Entry Enroll Summary∗58 Expert Programming Mode Procedures Completing Zone ProgrammingTo Delete a Serial Number Zone ProgrammingSerial number ConfirmTemplate Display Wireless Key Programming TemplatesTemplate Number Partition5804BD 2-Way Wireless Key Transmitter Wireless Key Predefined Default TemplatesWireless Key Transmitter Not ConfirmedProgramming Output Devices About Output Device Programming *79/*80 Menu ModeMenu Mode Output Device Mapping Output IdentificationRelay Position Output TypeModule Addresses Output Function No Menu Mode Defining Output FunctionsActivated By = off = Change Device State = Close for 2 seconds Output Action01-08 = zone list ∗ to continue = Stay ClosedAbout Zone Lists *81 Menu Mode Zone List ProgrammingFunction Key About Function Keys *57 Menu ModeProgramming Function Keys Partition NumbeAbout Descriptor Programming *82 Menu Mode Programming Zone Descriptors Menu Mode ∗82Accept Second Word Accept First WordSecond 3-Digit Index No Assigning Partition/Custom Message DescriptorsCharacter Ascii Chart For Adding Custom Words For Entering Zone DescriptorsSchedule Number Programming Installer and User SchedulesStart Time = repeat every third week 4 = repeat every fourth week Repeat OptionRandomize For events 01 Report Code Formats System Communication and OperationPanel Communication with Central Station DigitWhere Code for Type +1/4+1 Report Standard ExpandedSome event codes may not apply to certain control panels Ademco Contact IDCode Definition Attributes Values Keyfob must be enrolled in system first see Wireless KeySystem Security Codes Level User No FunctionsVoice Keypads Keypad CommandsKeypad Functions Function DescriptionSetting the Real-Time Clock Keys Displayed as Zone ∗ /1 ∗ /#Various System Trouble Displays Alpha Display Fixed Disp MeaningInstallation and Setup Guide Checking Transmitter Enrollment Sniffer Mode Testing the SystemAbout Test Procedures System TestDialer Communication Test and Periodic Test Reports Go/No Go Test ModeAutomatic Standby Battery Tests Automatic Periodic Test ReportElectrical Specifications & AccessoriesSecurity Control CommunicationWire Smoke Detector Detector TypeCompatible 5800 Series Transmitters Table Series Transmitter Input Loop IdentificationModel Product Input Type Description Can be used to turn the burglary protection on and off 5827 Wireless KeypadTo be transmitted Regulatory Agency Statements Industrie CanadaUL Notices Page Installation and Setup Guide Page Installation and Setup Guide Limitations and Warranty Limitations of this Alarm System10-8 Index 10-10 Summary of Connections Limited Warranty K5305-1V5 10/04 Rev. a