Installation and Setup Guide
*161 Pager 1 Characters
Enter up to 16 characters.
Up to 16 optional characters may be sent as a prefix to the
The 16 characters may be composed of the following: PIN number, Subscriber account number,
∗(enter # + 11 to send ∗), # (enter # + 12 to send #), Pause (enter # + 13 to allow a
†Some paging systems require pause(s) before the prefix. The Pager format for the
XXX =
YYYY =
Display Example 1. 9 1 1 – 1 0 0 4 Indicates an alarm
(911)caused by a fault in zone 4 (0004) in part. 1.
Display Example 2. 1 0 2 – 2 0 0 5 Indicates the system is reporting a
*162 Pager 1 Report Options
0 = No reports sent; 1 = Open/close for all users enabled to page†; 4 = All alarms and troubles
5 = All alarms, troubles, and open/close for all users enabled to page
12 = Alarms and troubles for zones entered in zone list 9 13 = Alarms and troubles for zones listed in zone list 9 and open/close for all users enabled to page
Enter the types of reports to be sent to Pager 1 for each partition.
†Reports to pager only when arming (close)/disarming (open) from a keypad using a security code;
*163 Pager 2 Phone No.
up to 20 digits
If entering fewer than 20 digits, exit by pressing [∗] + next field number. To clear entries, press ∗163∗.
*164 Pager 2 Characters
up to 16 characters
See field ∗161 for explanation of entries. If fewer than 16 characters, exit by pressing [∗] and next field number. To clear entries, press ∗164∗.
*165 Pager 2 Report Options
See pager 1 reports, field *162 for entries, except use zone list 10
*166 Pager 3 Phone No.
VISTA-20P. Enter up to 20 digits
If entering fewer than 20 digits, exit by pressing [∗] + next field number. To clear entries, press ∗166∗.
*167 Pager 3 Characters
VISTA-20P. Enter up to 16 characters
See field ∗161 for explanation of entries. If fewer than 16 characters, exit by pressing [∗] and next field number. To clear entries, press ∗167∗.
*168 Pager 3 Report Options
*169 Pager 4 Phone No.
If entering fewer than 20 digits, exit by pressing [∗] + next field number. To clear entries, press ∗169∗.
*170 Pager 4 Characters
See field ∗161 for explanation of entries. If fewer than 16 characters, exit by pressing [∗] and next field number. To clear entries, press ∗170∗.
*171 Pager 4 Report Options
*172Pager Delay Option for Alarms
0 = none; 2 = 2 minutes; 1 = 1 minute; 3 = 3 minutes This field determines the delay of alarm reports to the pager. This gives the Central Station enough time to verify the alarm report that it received, before the dialer attempts to dial the pager.
This delay is for ALL pagers in the system
Miscellaneous System Fields
*174 Clean Me Option
0 = disable; 1 = enable
This is a maintenance feature for ESL
*177 Device Duration 1, 2
0 = 15 secs | 4 | = 90 secs | 8 = 4 min | #+12 = 8 min |
1 = 30 secs | 5 | = 2 min | 9 = 5 min | #+13 = 10 min |
2 = 45 secs | 6 | = | #+10 = 6 min | #+14 = 12 min |
3 = 60 secs | 7 | = 3 min | #+11 = 7 min | #+15 = 15 min |
These entries set the duration for output action options 5 (duration 1) and 6 (duration 2) programmed in ∗80 Output Function Programming.
*181 50/60 Hz AC Operation
0 = 60 Hz; 1 = 50 Hz
Select the type of AC power applied to the control (option is used for