F220 Series Detectors with F220-B6RS Bases

Install the Bases en 11

 

 

3.2.4Four-wire Loop Termination

One D275 End-of-Line Module (refer to Figure 3.5 on page 19) or F220-B6E Power Supervision Base (refer to Figure 3.4 on page 18) is required for each loop when using four-wire bases.

3.3Wire Optional Remote Annunciators

If using the optional DRA-5 Remote Alarm Indicator, connect the positive (red) wire to terminal b1 and the negative wire (white) to terminal c (refer to Figure 3.1).

 

 

 

 

1

 

 

 

 

DRA-5

b2

b1

a1/a2

c

2

 

 

 

 

4 3

 

 

 

5

2

 

 

 

1

 

 

 

 

 

 

1.Red wire to Terminal b1 on base

2.White wire to Terminal c on base

Fig. 3.1 Optional DRA-5 Remote Annunciator Wiring

3.4Wire F220-B6RS Sounder Bases

The F220-B6RS has a built-in sounder that can be set to operate in one of four ways through a combination of wiring and DIP switch settings (refer to Figure 3.2, Item 3 on page 14 and Table 3.2 on page 15).

Bosch Security Systems, Inc.

Installation Manual

F.01U.029.847 -01 2007.02

Image 11
Contents F220 Series Detectors with F220-B6RS Base Trademarks Required Maintenance and TestingLegal Compatible Control Panels General InformationBase Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector Features4 F220 Series Smoke Detector Heads Technical SpecificationsGeneral Specifications Electrical Supervision Install the BasesBase Specifications Detector SpecificationsPage EOL Resistors Wire the BasesLoop Wiring Specifications Terminal ConnectionsFour-wire Loop Termination Wire Optional Remote AnnunciatorsWire F220-B6RS Sounder Bases NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire F220-B6E Power Supervision Base Wire Power Supervision ModulesF220-B6E D275 Wire D275 Power Supervision ModuleOptional Locking Bar Install the Detector HeadsMount the Detector Heads LED Keyed. Do not force them onto the mounting bases Detector HeadSet Detector Modes Test ModeSensitivity Mode Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationTest Each Detector Activate an Alarm at Each DetectorReset the Control Panel Test any CO Sensors Test the Alarm LoopPerform Nfpa 72 Required Testing USA