Bosch Appliances F220-B6RS installation manual Wire D275 Power Supervision Module

Page 19

F220 Series Detectors with F220-B6RS Bases

Install the Bases en 19

 

 

The alarm loop relay (Form A, Terminals 1 and 2) and the power supervision relay (Terminal 3 and 4) are rated for 0.5 A at 120 VAC/DC for resistive loads.

!

CAUTION! Do not connect relays to inductive or

capacitive loads. Use with resistive loads only.

 

3.5.2 Wire D275 Power Supervision Module

When a D275 Module is used with 24 VDC systems, connect the yellow wire to the output terminal (b1 or b2). The red wire remains unconnected (refer to Figure 3.5 on page 19).

 

1

 

3

2

D275

2

 

 

 

 

4

+12 VDC

7

5

+24 VDC

 

6

Common (-)

1.

EOL resistor (refer to the

 

to Terminal 1 on the last

 

control panel’s

 

base on the loop.

 

installation instructions

4.

Red wire is not used.

 

for specifications).

5.

Yellow wire to Terminal b1

2.

The positive (+) and

 

on last base on loop for

 

negative (-) IDC wires

 

24 VDC systems.

 

(blue) from the D275.

6.

Black wire (common) to

3.

Connect the positive (+)

 

Terminal a1/a2 on last

 

IDC wire through the EOL

 

base on loop.

 

resistor to Terminal 2 and

7.

Power loop

 

the negative (-) IDC wire

 

 

 

 

 

 

Fig. 3.5 Wiring a D275 Power Supervision Module as a Loop Terminator

Bosch Security Systems, Inc.

Installation Manual

F.01U.029.847 -01 2007.02

Image 19
Contents F220 Series Detectors with F220-B6RS Base Legal Required Maintenance and TestingTrademarks Compatible Control Panels General InformationBase Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector FeaturesGeneral Specifications Technical Specifications4 F220 Series Smoke Detector Heads Electrical Supervision Install the BasesBase Specifications Detector SpecificationsPage EOL Resistors Wire the BasesLoop Wiring Specifications Terminal ConnectionsWire F220-B6RS Sounder Bases Wire Optional Remote AnnunciatorsFour-wire Loop Termination NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire F220-B6E Power Supervision Base Wire Power Supervision ModulesF220-B6E D275 Wire D275 Power Supervision ModuleMount the Detector Heads Install the Detector HeadsOptional Locking Bar LED Keyed. Do not force them onto the mounting bases Detector HeadSensitivity Mode Test ModeSet Detector Modes Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationReset the Control Panel Activate an Alarm at Each DetectorTest Each Detector Perform Nfpa 72 Required Testing Test the Alarm LoopTest any CO Sensors USA