Bosch Appliances F220-B6RS installation manual NAC Configurations

Page 12

12 en Install the Bases

F220 Series Detectors with F220-B6RS Bases

 

 

3.4.1NAC Configurations

In these configurations, the sounders are controlled and powered from the control panel’s NAC power circuit or a remote NAC power circuit. The positive (+) wire from the NAC or D132B Multi-use Reversing Relay Module connects to Terminal 5 and the negative (-) wire connects to Terminal 4 (refer to Figure 3.2, Item 3 on page 14). The sounders on the loop follow the NAC configuration programmed at the control panel. The DIP switches (refer to Figure 2.1, Item 15 on page 4) are set as shown in Table 3.1.

WARNING! DIP switches 1 and 2 must be either both on

! or both off. Having one on and the other off could result in incorrect operation including failure to alarm.

Position 1 and 2 off;

3 and 4 either both on or both off.

O N D I P

1 2 3 4

Control panel NAC circuit power is applied to the base to Terminals 4(+) and 5(-). The sounder follows the configuration of the NAC. The positions of switches 3 and 4 have no affect.

Table 3.1 NAC Configuration DIP Switch Settings

NAC Follower (Direct Wire) Configuration: The sounders on the loop follow the signal on the NAC terminals as pro- grammed at the control panel. Refer to the control panel's installation manual for NAC configuration instructions. This configuration requires an extra pair of supervised wires for the sounder circuit (refer to Figure 3.2, Item 3 on page 14).

Reverse Polarity Configuration: Tthe sounders in a loop activate due to reversed polarity on the power line. The output pattern is not controlled by the base in this operat- ing mode; it follows the signal on the head terminals as programmed at the controlpanel.

F.01U.029.847 -01 2007.02

Installation Manual

Bosch Security Systems, Inc.

Image 12
Contents F220 Series Detectors with F220-B6RS Base Required Maintenance and Testing LegalTrademarks General Information Compatible Control PanelsBase Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector HeadsTechnical Specifications General Specifications4 F220 Series Smoke Detector Heads Install the Bases Base SpecificationsDetector Specifications Electrical SupervisionPage Wire the Bases Loop Wiring SpecificationsTerminal Connections EOL ResistorsWire Optional Remote Annunciators Wire F220-B6RS Sounder BasesFour-wire Loop Termination NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire Power Supervision Modules Wire F220-B6E Power Supervision BaseF220-B6E Wire D275 Power Supervision Module D275Install the Detector Heads Mount the Detector HeadsOptional Locking Bar LED Detector Head Keyed. Do not force them onto the mounting basesTest Mode Sensitivity ModeSet Detector Modes Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationActivate an Alarm at Each Detector Reset the Control PanelTest Each Detector Test the Alarm Loop Perform Nfpa 72 Required TestingTest any CO Sensors USA