Bosch Appliances F220-B6RS Technical Specifications, 4 F220 Series Smoke Detector Heads

Page 7

F220 Series Detectors with F220-B6RS Bases

General Information en 7

 

 

2.2.4F220 Series Smoke Detector Heads

The F220 Series Smoke Detector Heads are UL Listed, open- area photoelectric smoke detectors that work with commercial fire protective signaling systems and household fire warning systems. Select the appropriate mounting base to configure the detectors for two-wire or four-wire versions (refer to

Section 2.1 F220-B6RS Detector Bases on page 3).

To verify power to the detector and a functioning smoke sampling circuitry, a dual color LED indicator flashes green every eight seconds when operating normally. It flashes once every four seconds when a trouble condition exists. If the detector determines an alarm condition exists, the LED changes from flashing green to steady red. The detector returns to normal after the alarm condition is cleared and power is interrupted.

Throughout its normal life cycle, the smoke detector monitors and periodically adjusts itself to keep the sensitivity at its factory calibrated level. When excessively dirty, the detector’s LED flash rate changes from an eight second flash rate to a four second rate. If CleanMe is selected, the detector sends a CleanMe signal to the compatible control panel to indicate a dirty smoke detector.

Refer to Section 4.3 Set CleanMe Feature on page 24.

2.3Technical Specifications

2.3.1General Specifications

Air Velocity

4000 ft/min (1200 m/min) maximum

 

 

Operating

+32°F to 100°F (0°C to 38°C)

Temperature

 

 

 

Relative

0% to 95% (non-condensing)

Humidity

 

 

 

Table 2.3 Specifications - Detectors and Bases

Bosch Security Systems, Inc.

Installation Manual

F.01U.029.847 -01 2007.02

Image 7
Contents F220 Series Detectors with F220-B6RS Base Legal Required Maintenance and TestingTrademarks Compatible Control Panels General InformationBase Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector FeaturesGeneral Specifications Technical Specifications4 F220 Series Smoke Detector Heads Electrical Supervision Install the BasesBase Specifications Detector SpecificationsPage EOL Resistors Wire the BasesLoop Wiring Specifications Terminal ConnectionsWire F220-B6RS Sounder Bases Wire Optional Remote AnnunciatorsFour-wire Loop Termination NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire F220-B6E Power Supervision Base Wire Power Supervision ModulesF220-B6E D275 Wire D275 Power Supervision ModuleMount the Detector Heads Install the Detector HeadsOptional Locking Bar LED Keyed. Do not force them onto the mounting bases Detector HeadSensitivity Mode Test ModeSet Detector Modes Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationReset the Control Panel Activate an Alarm at Each DetectorTest Each Detector Perform Nfpa 72 Required Testing Test the Alarm LoopTest any CO Sensors USA