F220 Series Detectors with F220-B6RS Bases

Test the Installation en 25

 

 

be met by visually inspecting the detector and checking the flash rate of the LED.

NOTE! Perform the visual check before resetting power.

i After a reset the trouble indicators clear for 70 seconds. After 70 seconds, if the detector is in a trouble condition, trouble indications begin again.

A unit with CleanMe activated double flashes (two flashes within a half second of each other) every eight seconds. A normally operating unit flashes once every eight seconds. If a detector is in a trouble condition due to a dirty lens or a sensor malfunction, it single or double flashes every four seconds. If enabled, the CleanMe trouble signal is sent. If the calibration is out of range for more than 24 hours, the green LED on the detector flashes approximately once every four seconds.

5 Test the Installation

5.1Inspect the Installation

1.Check the wiring from the control panel to the last head on each run for proper polarity and continuity.

2.Terminate each run with an EOL resistor as specified by the control panel manufacturer.

3.Terminate four-wire runs with EOL power supervision modules or F220-B6E bases.

4.Apply power to the system. Check for alarms and troubles.

5.Note which detectors alarmed (if any), shut down the system, remove alarmed detectors from their bases, and recheck the bases for proper wiring.

6.If the problem persists, determine if the problem is caused by the detector or the base. Replace the affected detectors or bases with known good units.

7.If a system alarm occurs with no detector alarms present, remove all detectors and check the wiring at each base.

8.Check the wiring of each EOL resistor and EOL module.

Bosch Security Systems, Inc.

Installation Manual

F.01U.029.847 -01 2007.02

Image 25
Contents F220 Series Detectors with F220-B6RS Base Legal Required Maintenance and TestingTrademarks Compatible Control Panels General InformationBase Features About F220 Series Detector Heads F220 Series Detectors3 F220 Series Heat Detector Heads 2 F220 Series Detector FeaturesGeneral Specifications Technical Specifications4 F220 Series Smoke Detector Heads Base Specifications Install the BasesDetector Specifications Electrical SupervisionPage Loop Wiring Specifications Wire the BasesTerminal Connections EOL ResistorsWire F220-B6RS Sounder Bases Wire Optional Remote AnnunciatorsFour-wire Loop Termination NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire F220-B6E Power Supervision Base Wire Power Supervision ModulesF220-B6E D275 Wire D275 Power Supervision ModuleMount the Detector Heads Install the Detector HeadsOptional Locking Bar LED Keyed. Do not force them onto the mounting bases Detector HeadSensitivity Mode Test ModeSet Detector Modes Flash Rate and Trouble Indication Set CleanMe FeatureInspect the Installation Test the InstallationReset the Control Panel Activate an Alarm at Each DetectorTest Each Detector Perform Nfpa 72 Required Testing Test the Alarm LoopTest any CO Sensors USA