26 en Test the Installation

F220 Series Detectors with F220-B6RS Bases

 

 

9.When the system is alarm free, check each detector to ensure that the green LED indicator flashes approximately every eight seconds. This verifies the detector is receiving power and operating properly.

NOTE! If a heat detector LED flashes at a rate of

4 flashes/sec, the detector is either cold (below +32°F

i [0°C]), out of sensitivity range, or defective. If a smoke detector flashes at a rate of 4 flashes/sec, it is either out of sensitivity range or defective.

5.2Test Each Detector

Test each detector to ensure it causes a control panel alarm. Reset the control panel after each test.

5.2.1Activate an Alarm at Each Detector

To cause heat detectors to alarm either:

Activate the internal reed switch by placing a magnet horizontally against the T mark on the mounting skirt and holding it there for three consecutive LED flashes, or

Expose the thermistor to a heat source such as a hair dryer or a shielded heat lamp until the detector alarms and the

alarm LED lights .

To cause smoke detectors to alarm either:

Activate the internal reed switch by placing a magnet horizontally against the T mark on the mounting skirt and holding it there for three consecutive LED flashes, or

Use a UL Listed aerosol smoke detector tester to simulate an alarm. Follow the instructions provided with the aerosol smoke detector tester.

5.2.2Reset the Control Panel

When a detector alarms, the red LED indicator activates and latches into the ON position. Clear the alarm by momentarily removing power before proceeding to the next detector.

F.01U.029.847 -01 2007.02

Installation Manual

Bosch Security Systems, Inc.

Image 26
Contents F220 Series Detectors with F220-B6RS Base Trademarks Required Maintenance and TestingLegal General Information Compatible Control PanelsBase Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector Heads4 F220 Series Smoke Detector Heads Technical SpecificationsGeneral Specifications Detector Specifications Install the BasesBase Specifications Electrical SupervisionPage Terminal Connections Wire the BasesLoop Wiring Specifications EOL ResistorsFour-wire Loop Termination Wire Optional Remote AnnunciatorsWire F220-B6RS Sounder Bases NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire Power Supervision Modules Wire F220-B6E Power Supervision BaseF220-B6E Wire D275 Power Supervision Module D275Optional Locking Bar Install the Detector HeadsMount the Detector Heads LED Detector Head Keyed. Do not force them onto the mounting basesSet Detector Modes Test ModeSensitivity Mode Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationTest Each Detector Activate an Alarm at Each DetectorReset the Control Panel Test any CO Sensors Test the Alarm LoopPerform Nfpa 72 Required Testing USA