Bosch Appliances F220-B6RS installation manual Wire the Bases, Terminal Connections, EOL Resistors

Page 10

10 en Install the Bases

F220 Series Detectors with F220-B6RS Bases

 

 

3.2Wire the Bases

CAUTION! When wiring bases, all terminal screws

!including those not wired must be tightened to prevent loose screw heads from making intermitent electrical

contact with the detector head.

3.2.1Terminal Connections

WARNING! Do not twist or loop the wires around the terminals. In and out wires for terminal connection must

!be cut, stripped, and inserted as individual ends.

NOTE! Bring the positive (+) wires in on terminal b2 and

i out from terminal b1. Use a consistent pattern, inputting on b2 and outputting from b1. The negative (-) wires input and output from the same terminal (a1/a2).

3.2.2EOL Resistors

Use the EOL resistors supplied or specified by the control panel manufacturer. This applies to all loop terminations including the D275 Module and the F220-B6E Power Supervision Base.

3.2.3Loop Wiring Specifications

In a four-wire system, the maximum loop length and number of bases that can be placed on a loop depend on the voltage drop on the power circuit. Use standard voltage drop calculations to ensure that the last detector on the loop meets the minimum voltage requirement of at least 16 V.

F.01U.029.847 -01 2007.02

Installation Manual

Bosch Security Systems, Inc.

Image 10
Contents F220 Series Detectors with F220-B6RS Base Legal Required Maintenance and TestingTrademarks General Information Compatible Control PanelsBase Features F220 Series Detectors About F220 Series Detector Heads2 F220 Series Detector Features 3 F220 Series Heat Detector HeadsGeneral Specifications Technical Specifications4 F220 Series Smoke Detector Heads Detector Specifications Install the BasesBase Specifications Electrical SupervisionPage Terminal Connections Wire the BasesLoop Wiring Specifications EOL ResistorsWire F220-B6RS Sounder Bases Wire Optional Remote AnnunciatorsFour-wire Loop Termination NAC Configurations Local Configurations F220-B6RS Local Configuration DIP Switch Settings D275 Wire Power Supervision Modules Wire F220-B6E Power Supervision BaseF220-B6E Wire D275 Power Supervision Module D275Mount the Detector Heads Install the Detector HeadsOptional Locking Bar LED Detector Head Keyed. Do not force them onto the mounting basesSensitivity Mode Test ModeSet Detector Modes Set CleanMe Feature Flash Rate and Trouble IndicationTest the Installation Inspect the InstallationReset the Control Panel Activate an Alarm at Each DetectorTest Each Detector Perform Nfpa 72 Required Testing Test the Alarm LoopTest any CO Sensors USA